Siemens RUGGEDCOM RMC40 Installation Manual page 30

4-port unmanaged ethernet switch
Hide thumbs Also See for RUGGEDCOM RMC40:
Table of Contents

Advertisement

Chapter 6
Certification
Test
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 60255-5
a
Siemens specified severity level.
IEEE 1613 EMC Immunity Type Tests
NOTE
The RUGGEDCOM RMC40 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports.
ESD
Radiated RFI
Fast Transient
Oscillatory
24
Description
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
AC Power Ports
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Enclosure Ports
40 A/m continuous, 1000 A/m for 1 s
DC Power Ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
AC Power Ports
30% for 1 period, 60% for 50 periods
100% for 5 periods,
100% for 50 periods
Signal Ports
2 kV  (Fail-Safe Relay output)
DC Power Ports
AC Power Ports
Signal Ports
5 kV  (Fail-Safe Relay Output)
DC Power Ports
AC Power Ports
Installation Guide
Test Levels
10 V
10 V
10 V
10 V
1000 A/m for 1 s
1.5 kV
2 kV
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV common mode @ 1MHz
EMC and Environmental Type Tests
RUGGEDCOM RMC40
Severity Levels
3
4
3
3
3
3
a
Note
5

Advertisement

Table of Contents
loading

Table of Contents