V Clean the sealing faces of the boiler bosses [1] with a
cloth soaked in white spirit.
V Evenly coat the boiler boss sealing faces with red lead
putty.
V Coat the joint lip/groove [2] with adhesive (primer).
5.1.2
Driving boss liners home
V Clean the boss liners with a cloth soaked in white spirit.
V Evenly coat the boss liners with red lead putty.
V Insert the boss liners straight into the upper and lower
hub of the rear section and hammer home securely with
alternate heavy blows.
Leave the two boss liners protruding approx.
30 mm from the boiler boss in each case.
V Remove any burrs with a file.
Logano G225/Logano plus GB225 - We reserve the right to make any changes due to technical modifications.
Boiler block assembly
1
Fig. 6
Coating the boiler hubs with red lead putty
1
Boiler boss sealing face
2
Packing groove
2
Fig. 7
Driving boss liners home
1
Boss liner in the upper boiler hub
2
Boss liner in the lower boiler hub
5
1
2
6 720 615 876-06.1RS
1
6 720 615 876-07.1RS