Mitsubishi FR-A500 Series Instruction Manual page 203

Transistorized inverter: fr-a520-0.4k to 55k(-na) and fr-a540-0.4k to 55k(-na)(-ec)
Hide thumbs Also See for FR-A500 Series:
Table of Contents

Advertisement

Operation Panel
Indication
Name
Description
Check point
Corrective action
(2) Minor fault
When the protective function is activated, the output is not shut off. You can make parameter setting to output
the light fault signal. (Set "98" in any of Pr. 190 to Pr. 195 (output terminal function selection). Refer to page
150)
Operation Panel
Indication
Name
Description
Check point
Corrective action
(3) Warnings
Operation Panel
Indication
Name
Description
Check point
Corrective action
Note 5: The stall prevention operation current may be set as desired. It is factory-set to 150%.
E.ECT
Wire break detection
The inverter output is stopped if the encoder signal is turned off during
orientation, PLG feedback or vector control executed with the FR-A5AP.
Check for encoder signal wire break.
Repair wire break.
FN
Fan fault
For the inverter, which contains a cooling fan, FN appears on the operation panel
when the cooling fan stops due to a fault or operates differently from the setting
of Pr. 244 "cooling fan operation selection".
Check the cooling fan for a fault.
Change the fan.
OL
Stall prevention (Over current)
If a current of more than 150% (Note 5) of the rated inverter
current flows in the motor, this function stops the increase in
During
frequency until the overload current reduces to prevent the
acceleration
inverter from resulting in overcurrent shut-off. When the
overload current has reduced below 150%, this function
increases the frequency again.
If a current of more than 150% (Note 5) of the rated inverter
current flows in the motor, this function lowers the frequency
During constant-
until the overload current reduces to prevent overcurrent
speed operation
shut-off. When the overload current has reduced below
150%, this function increases the frequency up to the set
value.
If a current of more than 150% (Note 5) of the rated inverter
current flows in the motor, this function stops the decrease in
During
frequency until the overload current reduces to prevent the
deceleration
inverter from resulting in overcurrent shut-off. When the
overload current has reduced below 150%, this function
decreases the frequency again.
Check the motor for use under overload.
The acceleration time may change. Increase the stall prevention operation level
using Pr. 22 "stall prevention operation level" or make the stall prevention
inoperative using Pr. 156 "stall prevention operation selection".
189
PROTECTIVE FUNCTIONS
FR-PU04
No encoder signal
FR-PU04
FR-PU04
Fan fault
OL
5