(3) Read Pr. 903 and show the current setting of the gain frequency.
(Pr. 902, Pr. 904 and Pr. 905 can also be adjusted similarly.)
!Parameter setting mode
Using the
FR-DU04
MON
Most significant
digit flickers.
Current setting of gain frequency
FR-DU04
MON
(4) Set a gain frequency in Pr. 903 and show the analog voltage A/D value across terminals 2-5 in %.
(when the frequency is set to 80Hz)
Current setting of
gain frequency
FR-DU04
MON
key, choose the "parameter setting mode" as in (2)-1).
MODE
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
SET
Middle digit
flickers.
×9
times
SET
0 to 9
CONTROL PANEL
Hz
A
V
EXT
PU
REV
FWD
!Changing the gain
frequency
FR-DU04
CONTROL PANEL
Hz
A
V
EXT
PU
MON
EXT
REV
FWD
REV
Press
change the set frequency.
!
Analog voltage A/D value (%)
across terminals 2-5
FR-DU04
MON
EXT
REV
In any of the methods in (5) to (7) on the following page,
continue the setting until the analog voltage A/D value
flickers. If you end the setting here, the gain frequency
change will not be reflected.
179
Least significant
digit flickers.
SET
0 to 9
CONTROL PANEL
Hz
A
V
PU
FWD
to
Press for 1.5 s
SET
CONTROL PANEL
Hz
A
V
PU
FWD
PARAMETERS
×3
times
SET
4