Online Auto Tuning Selection (Pr. 95) - Mitsubishi FR-A500 Series Instruction Manual

Transistorized inverter: fr-a520-0.4k to 55k(-na) and fr-a540-0.4k to 55k(-na)(-ec)
Hide thumbs Also See for FR-A500 Series:
Table of Contents

Advertisement

! To enter the Pr. 92 and Pr. 93 motor constants in [mH]
<Operating procedure>
1. Set any of the following values in Pr. 71:
• Standard motor....................................................................................... Pr. 71 = "0"
• Constant-torque motor ........................................................................... Pr. 71 = "1"
• Mitsubishi standard motor SF-JR 4 poles (1.5kW (2HP) or less) .......... Pr. 71 = "20"
2. Set "801" in Pr. 77.
(Only when the Pr. 80 and Pr. 81 settings are other than "9999", the parameter values of the motor
constants (Pr. 90 to Pr. 94) can be displayed. Though the parameter values of other than Pr. 90 to
Pr. 94 can be displayed, they are parameters for manufacturer setting and shall not be changed.)
3. In the parameter setting mode, read the following parameters and set desired values:
Parameter
Number
90
Motor constant R1
91
Motor constant R2
92
Motor constant L1
93
Motor constant L2
94
Motor constant X
4. Return the Pr. 77 setting to the original value.
5. Refer to the following table and set Pr. 84:
Parameter
Number
84
Rated motor frequency
Note: 1. Pr.90 to Pr. 94 values may only be read when the Pr. 80 and Pr. 81 settings are other than
"9999" (advanced magnetic flux vector control selected).
2. Set "9999" in Pr. 90 to Pr. 94 to use the standard motor constants (including those for the
constant-torque motor).
Pr. 89 "
" Refer to Pr. 80.
" "

4.2.39 Online auto tuning selection (Pr. 95)

Pr. 95 "online auto tuning selection"
By online auto tuning, the motor conditions are tuned rapidly at the start. This enables precise operation
unaffected by motor temperatures and steady high-torque operation down to super-low speed. After setting
the Pr. 80 and Pr. 81 values, select online auto tuning with Pr. 95.
! Online auto tuning
Use this function when steady high-torque operation is required for low-speed operation under advanced
magnetic flux vector control.
• Before starting the online auto tuning, perform the offline auto tuning. Data must be calculated.
Name
Setting Range
0 to 50Ω, 9999
0 to 50Ω, 9999
0 to 1000mH, 9999
0 to 1000mH, 9999
0 to 100%, 9999
Name
Setting Range
50 to 120Hz
Setting
Increments
0.001Ω
0.001Ω
0.1mH
0.1mH
0.1%
Setting
Increments
0.01Hz
Related parameters
Pr. 71 "applied motor"
Pr. 80 "motor capacity"
Pr. 81 "number of motor poles"
Pr. 83 "rated motor voltage"
Pr. 84 "rated motor frequency"
Pr. 89 "speed control gain"
Pr. 90 to Pr. 94 (motor constants)
Pr. 96 "auto tuning setting/status"