Mitsubishi FR-A500 Series Instruction Manual page 136

Transistorized inverter: fr-a520-0.4k to 55k(-na) and fr-a540-0.4k to 55k(-na)(-ec)
Hide thumbs Also See for FR-A500 Series:
Table of Contents

Advertisement

5) Waiting time
Specify the waiting time between the receipt of data at the inverter from the computer and the transmission
of reply data. Set the waiting time in accordance with the response time of the computer between 0 and
150ms in 10ms increments (e.g. 1 = 10ms, 2 = 20ms).
Computer
Inverter
Inverter
Computer
Note : When Pr. 123 "waiting time setting" , 9999, create the communication request data
with no "waiting time" in the data format. (The number of characters is decreased by 1.)
6) Response time
Computer
Inverter
Inverter
Computer
Computer
Inverter
Inverter
Computer
[Data sending time calculation expression]
1
Number of data characters
Communication speed
(bps)
Communication specification
Name
Number of Bits
1 bit
Stop bit length
2 bits
7 bits
Data length
8 bits
Yes
1 bit
Parity check
No
0 bits
In addition to the bits in the above table, 1 bit is required for the start bit.
Minimum total number of bits ... 9 bits
Maximum total number of bits ... 12 bits
Data sending time
(refer to the following calculation expression)
Inverter data processing time = waiting time + data check time
STX
Data sending time
Data sending time
(refer to the following calculation expression)
Inverter data processing time = waiting time + data check time
Data sending time (refer to the following calculation expression)
Communication specification
(Refer to page 121)
Inverter data processing time
=waiting time
(set value×10ms)
(set value 10ms)
ACK
ENQ
10ms or
10ms or
more required
more required
(refer to the following calculation expression)
(set value 10ms)
ENQ
10ms or
more required
(Total number of bits)
= Data sending time (s)
(See below)
123
PARAMETERS
+ data check time
(12ms)
(12ms)
(12ms)
4