Instructions For Compliance With U.s. And Canadian Electrical Codes - Mitsubishi FR-A500 Series Instruction Manual

Transistorized inverter: fr-a520-0.4k to 55k(-na) and fr-a540-0.4k to 55k(-na)(-ec)
Hide thumbs Also See for FR-A500 Series:
Table of Contents

Advertisement

2.3.7 Instructions for compliance with U.S. and Canadian Electrical
Codes
(Standard to comply with: UL 508C)
( 1 ) Installation
The above types have been approved as products for use in enclosure and approval tests were conducted
under the following conditions.
• • • • 200V class
Minimum Enclosure Volume
Inverter Model
(Ratio of enclosure volume to
inverter volume)
FR-A520-0.4K
FR-A520-0.75K
FR-A520-1.5K
FR-A520-2.2K
FR-A520-3.7K
FR-A520-5.5K
FR-A520-7.5K
FR-A520-11K
FR-A520-15K
FR-A520-18.5K
FR-A520-22K
FR-A520-30K
FR-A520-37K
FR-A520-45K
FR-A520-55K
• • • • 400V class
Design the enclosure so that the ambient temperature, humidity and ambience of the inverter will satisfy the
above specifications. (Refer to page 206)
( 2 ) Branch circuit protection
For installation in United States, branch circuit protection must be provided, in accordance with the National
Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided in accordance with the Canada
Electrical Code and any applicable provincial codes.
( 3 ) Short circuit ratings
• • • • 200V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 5 or 10kA rms Symmetrical Amperes, 230
or 500 Volts Maximum.
• • • • 400V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 10kA rms Symmetrical Amperes, 500
Volts Maximum.
( 4 ) Wiring of the power supply and motor
Screw the cables wired to the input (R, S, T) <L
the inverter to the specified tightening torque using UL-recognized, 75° or higher rated copper wires and
round crimping terminals. Crimp the crimping terminals with the crimping tool recommended by the terminal
maker.
Air Vent Area
(Ratio of air vent area in enclosure
top and bottom to enclosure
surface area)
150
150
245
245
245
245
245
245
370
370
370




, L
, L
1
2
40
INSTALLATION AND WIRING
External Cooling Fan
(The following number of fans of
100cfm wind pressure are installed
10cm above the inverter top)
5.8
5.8
1.5
1.5
1.5
1.5
1.5
1.5
2.6
2.6
2.6




> and output (U, V, W) terminals and control circuit of
3
0
0
1
1
1
1
1
2
2
2
2
2
2
2
2
2