Horizontal Terminations; Flex Vent 4" X 6-7/8 - Regency CC40LE-NG Owners & Installation Manual

City series zero clearance direct vent gas fireplace
Table of Contents

Advertisement

Horizontal Terminations

"

Flex Vent 4" x 6-7/8

These venting systems, in combination with the CC40LE/CC40RE Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system
by Warnock Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent
Termination Locations" section.
Regency
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the CC40LE/CC40RE using a flexible vent.
®
FPI Kit #
Length
Contains:
1.
#946-513
2 Feet
6-7/8" flexible outer liner (Kit length)
2.
4" flexible inner liner (Kit length)
3.
spring spacers
4.
thimble
#946-515
4 Feet
5.
AstroCap termination cap
6.
screws
7.
tube of Mill Pac
#946-516
10 Feet
8.
plated screws
9.
S.S. screws #8 x 1-1/2" drill point
Notes:
1. Liner sections should be continuous without any
joints or seams.
2. Only Flex pipe purchased from Regency
used for Flex installations
3. Horizontal vent must be supported every 3 feet.
4. Regency
Direct Vent System (Flex) is only approved
®
for horizontal terminations.
5. Flex system can only be used up to a maximum
continuous vent length of up to 10 feet. If longer
runs are required, rigid pipe must be used.
may be
®
installation
Vent Guard - if required*
(Part #946-506/P)
City Series |
31