Regency City Series Owners & Installation Manual

Zero clearance direct flue gas fireplace
Hide thumbs Also See for City Series:
Table of Contents

Advertisement

Quick Links

Zero Clearance Direct Flue Gas Fireplace
STYLE
Left Corner
Right Corner
Warning
Fire or explosion Hazard
failure to follow safety warnings exactly could result in serious
injury, death, or property damage.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
• Do not touch any electrical switch: do not use any phone in your building.
Leave the building immediately.
• Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Installer: Please complete the details on the back cover and leave this manual with the homeowner.
920-124
City Series
MODEL
ACC40LENG / ACC40LELP / ACC40LEULPG
ACC40RENG / ACC40RELP / ACC40REULPG
Homeowner: Please keep these instructions for future reference.
®
Owners &
Installation Manual
LISTINGS AND CODE APPROVALS
These gas appliances have been
tested in accordance with AS/NZS
5263.0 & AS/NZS 5263.1.8:2016
and have been certified by IAPMO
for installation and operation as
described in these Installation and
Operating Instructions.
Must be installed as per AS/NZS5601.
Your unit should be serviced
annually by an authorised service
person.
www.regency-fire.com.au
PRIMARILY A DECORATIVE AND NOT A
HEATING APPLIANCE.
DO NOT MODIFY THIS APPLIANCE.
03.12.20

Advertisement

Table of Contents
loading

Summary of Contents for Regency City Series

  • Page 1 ® City Series Owners & Zero Clearance Direct Flue Gas Fireplace Installation Manual LISTINGS AND CODE APPROVALS These gas appliances have been tested in accordance with AS/NZS 5263.0 & AS/NZS 5263.1.8:2016 and have been certified by IAPMO for installation and operation as described in these Installation and Operating Instructions.
  • Page 2 fireplace at the flick of a switch. The ACC40LE / ACC40RE City Series have been approved by IAPMO for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow.
  • Page 3: Table Of Contents

    Horizontal Terminations ..........40 Venting Introduction .............41 Flueing Arrangement for Horizontal Terminations ..41 Horizontal Terminations ..........42 Horizontal Terminations ..........42 Vertical Terminations ...........44 Flueing Arrangement for Vertical Terminations ....45 Vertical Terminations ...........46 Unit Installation with Horizontal Termination ....47 City Series ACC40E |...
  • Page 4: Copy Of Data Badge

    10pt May 7/14: Changed wording on Line 3 as per AGA Dec 12/12: Removed redundant ‘do not’ from the last line | City Series ACC40E Mar. 3/09: Rev. A - added information Nov. 6/06: no changes to artwork.
  • Page 5: Dimensions (Left Corner)

    Note: Height Dimension may vary depending on the height of the leveling legs. Note: These units are non-load bearing. ALL PICTURES / DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY. ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS. City Series ACC40E |...
  • Page 6: Dimensions (Right Corner)

    Dimensions (Right Corner) 1203mm 587mm 616mm 102mm 172mm 475mm 448mm 1108mm 374mm 1091mm Note: Height Dimension may vary depending on the height of the leveling legs. Note: These units are non-load bearing. | City Series ACC40E...
  • Page 7: Important Message

    GLASS WITH THE GLASS VACUUM ALERTED TO THE HAZARDS OF HIGH HOLDERS SUPPLIED BY THE MANU- SURFACE TEMPERATURES, ESPE- City Series Direct Flue Fireplaces must be FACTURER. LOWER THE GLASS TO CIALLY THE FIREPLACE GLASS, AND installed in accordance with these instructions.
  • Page 8: General Safety Information

    14. Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance. 15. The appliance area must be kept clear and free of combustible materials, (gases and other flammable vapours and liquids). | City Series ACC40E...
  • Page 9: Lighting Procedure

    3. After approximately 4 seconds the spark ignition system will spark for 60 seconds to light the main burner. 4. The unit will turn on. * Not offered on all models. Continuous Pilot/Intermittent Pilot (CPI/IPI) selection See remote control instructions for details. City Series ACC40E |...
  • Page 10: Copy Of The Lighting Plate Instructions

    Part #: 920-216 - Side B Part #: 920-214 Colours: Black on white, except for parts indicated as being Red. | City Series ACC40E Punch out .25" hole top right corner where indicated. Colours: Black on Grey, except for parts indicated as being Red.
  • Page 11: Proflame Ii Remote Control Operating Instructions

    (*) The receiver may be independent or integral to the IFC hearth ap- pliance control module. The receiver instruction may not be indepen- dent when part of the IFC. Figure 2: Transmitter LCD Display Fig3: Battery Figure 3: Battery Compartment compartment. City Series ACC40E | 12.18.17 920-207...
  • Page 12 Transmitter LCD display will only show the room temperature (Fig. 6). At the same time the Receiver will turn off the appliance. A single “beep” from the Receiver confirms reception of the command. Figure 9 Figure 10 | City Series ACC40E 920-207 12.18.17...
  • Page 13 Down Arrow Key will turn the secondary burner off. A single “beep” will confirm reception of the command. will confirm the reception of the command. Figure 13 Figure 14 Figure 17 Figure 18 12.18.17 920-207 City Series ACC40E |...
  • Page 14 3. Reinstall battery removed in Step 1 while holding both buttons—keep holding buttons, then release the MODE button only. 4. The screen will show either "Clr" or "Set" as the first option available is to disable or enable a mode. | City Series ACC40E 920-207 12.18.17...
  • Page 15: Inner Glass Panel Installation / Removal

    firmly towards the back wall until the springs at the back wall are compressed. Top clamps in closed position Bottom clamps in closed position ACC40LE/ACC40RE shown Bottom Top clamps in channel open position Bottom side clamps in open position ACC40LE/ACC40RE shown City Series ACC40E |...
  • Page 16 8. To remove the glass panels—always remove the side panel(s) (for 3 sided units) before removing the front panel. 9. Reverse steps to remove glass. Open Closed Handle front panel with supplied vacuum clamps | City Series ACC40E...
  • Page 17: Outer Safety Glass Panel Installation / Removal

    Clockwise = bring panel in Counter clockwise= bring 2. Using the supplied vacuum clamps, lift the large front glass panel and panel out position it front and centre by manoeuvering up and underneath the front of the unit frame. City Series ACC40E |...
  • Page 18 Note: When removing panels, we recommend using the supplied glass clamps. Note: If the outer safety glass side panels angle too far inward or outward, remove the side glass panel and adjust on the panel angle bracket, see details on previous page. Panel angle bracket | City Series ACC40E...
  • Page 19: Maintenance Instructions

    For relighting, refer to lighting instructions. Keep fittings have been disturbed, and consequently Regency dealer only. Replacement glass is shipped the burner and control compartment clean by loosened. Also check mechanical supports brushing and vacuuming at least once a year.
  • Page 20: Installer's Information

    floor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation. Note: For flue terminations refer to "Exterior Flue Termination Locations" section. | City Series ACC40E...
  • Page 21: Installation Checklist

    The 3 prong plug will be located near the gas valve on the appliance. 9. Final check. Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to customer. City Series ACC40E |...
  • Page 22: Nailing Strips

    Once complete ensure that the access panel is reinstalled prior to any finishing. The ACC40LE/ACC40RE has 4 screws to remove access cover. See locations in diagram to the right. Access panel screws | City Series ACC40E...
  • Page 23 Fire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fireplace and flue Top View system be installed only in accordance with these instructions. Alcove City Series ACC40E |...
  • Page 24: Clearances

    Clearances Lo w framing with vents Low framing with vents in front/sides or top ACC40LE shown Floor to ceiling with top op Floor to ceiling with top opening ACC40LE shown | City Series ACC40E...
  • Page 25 Clearances Chase enclosed Full framing with low vents in front or sides ACC40LE shown ACC40LE shown Full framing with vents in front or sides City Series ACC40E |...
  • Page 26: Mantel Clearances

    Mantel Clearances Combustible mantel clearances from top of front facing are shown in the diagram on the right. 13mm Plasterboard, timber, timber panel, etc. 305mm 229mm 130mm Top of Bottomof Fireplace Fireplace Opening Opening 383mm | City Series ACC40E...
  • Page 27: Framing Dimensions (Left Corner)

    Header studs (installed on edge and flat) Note: This appliance must be in- stalled on a level and solid surface such as a plywood floor which must be the full width and depth of the appliance. City Series ACC40E |...
  • Page 28: Framing Dimensions (Right Corner)

    Header studs (installed on edge and flat) Note: This appliance must be in- stalled on a level and solid surface such as a plywood floor which must be the full width and depth of the appliance. | City Series ACC40E...
  • Page 29: Wall Board/Plasterboard Installation

    If desired finishing includes a painted wall, 100% acrylic latex, oil-based or standard acrylic paints may be used. Follow paint manufacturer’s instructions for paint and primer application. 30mm 22mm ACC40LE - screws in shaded area only 76mm 30mm ACC40RE - screws in shaded area only 22mm 76mm City Series ACC40E |...
  • Page 30: Framing And Finishing Inset Installations

    Ensure that no material encroaches anywhere in the area of the glass as these are defined by the finishing lip above, below and to the sides of this appliance. | City Series ACC40E...
  • Page 31: Optional Framing Kit Installation

    K 656-400 Unit nailing strips are not required and can be recycled when using the framing kit. Remove nailing fl anges City Series ACC40E | NOTE: CC40LE use holes corresponding with diamond shape. CC40RE use holes corresponding with square shape.
  • Page 32 7. Identify D, attach to back corner C with 2 screws as shown below. Part D Profi le 8. Identify E (see diagram below), attach E to front corner C with 2 screws as shown below. Part E Profi le | City Series ACC40E 919-773a 04.24.17...
  • Page 33 13. Attach K (center support) to E and H with 2 screws each. screws on each side. 11. Identify H and attach to both front corners C and F with 2 screws on each side. 04.24.17 919-773a City Series ACC40E |...
  • Page 34: Building Additional Framing Off Of The Framing Kit

    The framing must be strong enough to support the weight of all fi nishing material and must not put any weight on the fi replace. Holes for fi xing additional framing to kit 13 mm for plasterboard Leave gap between framing and unit trim for nishing material | City Series ACC40E...
  • Page 35: Tv Recessed Into Wall- Typical Installs

    TV Recessed Into Wall- Typical Installs Maximum TV Recess TV Flush with Hearth City Series ACC40E |...
  • Page 36: Exterior Flue Termination Locations

    Exterior Flue Termination Locations FIGURE 6.2 (in part): LOCATION OF FLUE TERMINALS OF BALANCED FLUE AS/NZ 5601, ROOM-SEALED, FAN ASSISTED OR OUTDOOR APPLIANCE | City Series ACC40E...
  • Page 37 4 For appliance not addressed above acceptance should be obtained from the Technical Regulator. 5 Minimum clearance d and e also apply to any combustion air intake openings of appliances. City Series ACC40E |...
  • Page 38: Wall Mount On / Off Switch And Installation

    11. Using the two (2) screws provided secure the cover plate to the Battery Holder. 12. For coding instructions, see full details in this manual. Proflame Battery Holder J-Box Battery Holder Slider Switch Wall Plate Diagram 1 | City Series ACC40E...
  • Page 39: Flue Restrictor Position

    Screw locations Set 0 (Full open) Factory set Flue restrictor location - inside top of firebox Diagram 1 Set 1 (Vent restrictor at 51mm) Set 2 (Vent restrictor at 44mm) Set 3 (Vent restrictor at 38mm) City Series ACC40E |...
  • Page 40: Horizontal Terminations

    S.S. screws #8 x 38mm drill point Notes: 1. Liner sections should be continuous without any joints or seams. ® 2. Only Flex pipe purchased from Regency may be used for Flex installations 3. Horizontal vent must be supported every 0.9m. Vent Guard - if required* (Part #946-506/P) ®...
  • Page 41: Venting Introduction

    Refer to the "Flue Restrictor Position" section for details on how to change the flue restrictor from the factory setting of Set 0 to Set 2 if required. Note: For horizontal terminations the Regency Direct Flue Flex System may be used for installations with a maximum continuous flue length of up to 3m. If longer runs are required, rigid pipe must be used.
  • Page 42: Horizontal Terminations

    Metal Products Ameri Flue Direct Flue, Security Secure Vent , ICC Excel, Selkirk Direct-Temp and Olympia Chimney. AstroCap is a proprietary trade- mark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Flue are registered and/or proprietary trademarks of Simpson Dura-Flue Co. Inc. | City Series ACC40E...
  • Page 43 1.5m 2.1m 0.3m between 90 is required. 1.5m 1.2m 2.1m elbows is required. 1.8m 2.4m 1.8m 1.5m 3.3m 2.4m Restrictor Set 0 - Factory Setting 2.1m 1.8m 3.6m 2.7m Restrictor Set 0 - Factory Setting City Series ACC40E |...
  • Page 44: Vertical Terminations

    Metal Products Ameri Flue Direct Flue, Security Secure Vent , ICC Excel, Selkirk Direct-Temp and Olympia Chimney. AstroCap is a proprietary trade- mark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Flue are registered and/or proprietary trademarks of Simpson Dura-Flue Co. Inc. | City Series ACC40E...
  • Page 45: Flueing Arrangement For Vertical Terminations

    Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 0 through to Set 3 if required. "THIS UNIT MUST ALWAYS TERMINATE / FLUE DIRECTLY TO THE OUTDOORS." City Series ACC40E |...
  • Page 46: Vertical Terminations

    1.2m and max. 2.4m total horizontal. 0.9m 1.2m 1.8m 1.2m 1.5m 2.1m Please note min. 0.3m between 90 1.5m 1.8m 2.4m elbows is required. 1.8m 2.1m 2.7m 2.1m 2.4m 3.0m Lengths do not include elbow indicated | City Series ACC40E...
  • Page 47: Unit Installation With Horizontal Termination

    3 supplied screws (drilling pilot holes will make this easier). 4. Level the fireplace and fasten it to the framing using nails or screws through the top and side nailing strips. Diagram 2 Diagram 4 Diagram 1 City Series ACC40E |...
  • Page 48 flex pipe and slip it over the outer flue connection) Wall Thimble 2 pieces collar of the flue terminal at least 35mm and french 254mm fasten with the 3 screws. Outer Diameter) Fourrures en bois | City Series ACC40E...
  • Page 49: Dura-Vent Vertical Termination

    A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the flue height may solve the problem. City Series ACC40E |...
  • Page 50: Vertical Termination 102Mm X 175Mm Flueing - Vertical Flex Flue Kit

    Note: The ceiling fi restop/fi restop spacer may be cut down to size if this Slide the inner pipe over adaptor and secure with 3 screws. shield is too high for the application. 12. Repeat Step 11 to secure outer fl ex. | City Series ACC40E...
  • Page 51 16. Install termination cap by twist locking it. 17. Secure the fl ashing to the roof using screws Diagram 3 Note: Any closets or storage spaces which the vent passes through must be enclosed. Diagram 3a 920-117 06.05.19 City Series ACC40E |...
  • Page 52: Vertical Flue Extension Kit

    Note: The ceiling firestop/firestop spacer may be cut down to size if this shield Storm Collar is too high for the application. Flashing Ceiling firestop Firestop spacer to prevent debris from falling into the ceiling Roof support Diagram 1 firestop Ceiling firestop Enclosure Ceiling firestop 920-118 06.05.19 Diagram 1a | City Series ACC40E...
  • Page 53: System Data

    (clockwise) with a flat screwdriver. Note: Screw Do not use open flame for leak testing. should be snug, but do not over tighten. City Series ACC40E |...
  • Page 54: Wiring Diagrams

    This appliance is equipped with a three-prong (earthing) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the earth- ing prong from this plug. | City Series ACC40E...
  • Page 55: Optional Fan Ducting Kit Installation

    City Series 40 ACB40E Optional Fan Ducting Kit Installation OPTIONAL FAN DUCTING KIT INSTALLATION LISTINGS AND CODE GENERAL INFORMATION Maximum Duct Run: 9.0m Kit Contains 4.5m APPROVALS The Fan Kit increases the effectiveness of your fireplace by dispersing warm air from the fireplace If you require more than 4.5m please purchase Fan...
  • Page 56 City Series 40 ACB40E OPTIONAL FAN KIT INSTALLATION NOTE: Installation of Fan Kit should be done prior Air Duct to installation of the wall. 2) Mount and secure the fan housing assembly to framing members, the front of the fan housing will protrude 12.7mm out of the wall so it may be finished...
  • Page 57: Fan Duct Extension Kit

    City Series 40 ACB40E installation OPTIONAL FAN KIT INSTALLATION Fan Duct Extension Kit FAN DUCT EXTENSION KIT In order to use the fan extension duct kit, you must have fan kit. This kit allows you to extend the fan duct to 9m.
  • Page 58: Inner Glass Panel I(Firebox Glass) Installation / Removal

    firmly towards the back wall until the springs at the back wall are compressed. Top clamps in closed position Bottom clamps in closed position ACC40LE/ACC40RE shown Bottom Top clamps in channel open position Bottom side clamps in open position ACC40LE/ACC40RE shown | City Series ACC40E...
  • Page 59 8. To remove the glass panels—always remove the side panel(s) (for 3 sided units) before removing the front panel. 9. Reverse steps to remove glass. Open Closed Handle front panel with supplied vacuum clamps City Series ACC40E |...
  • Page 60: Outer Safety Glass Panel (Barrier Glass) Installation / Removal

    Clockwise = bring panel in Counter clockwise= bring 2. Using the supplied vacuum clamps, lift the large front glass panel and panel out position it front and centre by manoeuvering up and underneath the front of the unit frame. | City Series ACC40E...
  • Page 61 Note: When removing panels, we recommend using the supplied glass clamps. Note: If the outer safety glass side panels angle too far inward or outward, remove the side glass panel and adjust on the panel angle bracket, see details on previous page. Panel angle bracket City Series ACC40E |...
  • Page 62: Propane/Ulpg Conversion Instructions

    9. Re-attach the Pressure Regulator wire (disconnected in Step 6), and re- situate the IFC, secure the screws that fasten the IFC Mounting Brackets. 10. Remove pilot hood by lifting up and off. Cable from motor 920-217 03.12.20 | City Series ACC40E...
  • Page 63 Pilot retainer clip Manifold Pressure High 2.60 kPa Manifold Pressure Low 0.63 kPa Orifice Size #54 DMS Maximum Input 24 MJ/h Installer Notice: Minimum Input 11.7 MJ/h These instructions must be left with the appliance City Series ACC40E | 920-217 03.12.20...
  • Page 64: Painted Panel Installation

    Note: Install inner safety glass prior to installation of outer panels-see instructions in manual 1. Attach Regency logo to the right hand side of outer front panel. The magnets will be positioned under the outer front base panel to 2. Install panel clips into the slots at the top of the back panel as shown.
  • Page 65: Enamel Panel Installation

    2. Install panel clips into the slots at the top of the back panel as shown. 5. Manoeuvre in side panel to the side wall of the unit—secure in place with 1 panel clip and 1 screw. Panel Clip 6. Reverse steps to remove panels. City Series ACC40E | 11.25.16 919-743...
  • Page 66 Note: Install inner safety glass prior to installation of outer panels-see instructions in manual 1. Attach Regency logo to the right hand side of outer front panel. The magnets will be positioned under the outer front base panel to secure the logo.
  • Page 67: Burner And Firebox Media Options

    1.6kg Crushed Iceburg chips Around burner 1.6kg * Media not supplied with unit - must be purchased separately. Natural / Ivory Stones + Fireglass 19mm Crushed black glass + Black Fireglass Starfire Fireglass + Iceburg chips City Series ACC40E |...
  • Page 68: Optional Driftwood Log Set Installation

    The logs are fragile, handle with care—never force into position. 4. Install Black Fireglass (680g) and glowing wool on the burner as shown below. 19mm away from the edge of the burner Burner covered with Fireglass and glowing wool Log 2 in position 06.05.19 920-114 | City Series ACC40E...
  • Page 69 Add lava rock sparsely around the perimeter of the burner. 11. Place Log 4—identify the pin locator and match with the left side pin on Log 1. Pin in Log 1 Completed Install City Series ACC40E | 920-114 06.05.19...
  • Page 70: Removable Plasterboard Guides

    4. Loosen 2 screws from inside the firebox to release the existing side plasterboard guide, remove guide and recycle. Loosen 2 screws from inside the firebox to remove the side plasterboard trim pieces | City Series ACC40E...
  • Page 71: First Fire

    2 mm Propane 7 mm Propane with Logs 7 mm Propane with Stones 7 mm ULPG Fully Open Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT covered under warranty City Series ACC40E |...
  • Page 72: Maintenance

    NOTE: Do not handle bulb with bare hands. Use packaging or a tissue to hold new bulb when replacing. Regency Part# 911-208 Oven Lamp Assembly G9 120V/25W Regency Part# 911-072 Replacement Bulb G9 120 Volt/25 watt | City Series ACC40E...
  • Page 73: Valve Replacement

    Front screw locations 8. Reverse steps 6-1 to complete. Back screw locations 6. Remove 16 screws in locations shown below. Remove 16 screws securing valve tray City Series ACC40E |...
  • Page 74: Main Assembly

    940-440/P Outer Safety Glass Side - Tempered Small 904-970 Magnet Cup 13 mm (Each) 940-437/P Flush Inner Ceramic Glass Small 948-223 Logo Plate Plastic Regency/Flame Silver 656-574/P Valve Assembly - NG 656-131 Logo Mounting Bracket 656-776/P Valve Assembly - LP...
  • Page 75 Crushed Glass Coal Black 19mm / 1.6kg 946-739 Firebeads Black 2.3kg Pkg 946-710 Stones -Slate/Grey Basalt Natural 6.8kg 946-711 Stones - Ivory/Tan Basalt Natural 6.8kg 657-991 Chase Flue Flush Front White 656-953 Chase Steel Framing Kit May not be exactly as shown City Series ACC40E |...
  • Page 76 656-045 Burner Surround 904-970 Magnet Cup 13 mm (Each) 940-485/P Outer Barrier Tempered Glass Assembly - Large 948-223 Logo Plate Plastic Regency/Flame Silver 940-436/P Flush Inner Ceramic Glass - Large 656-131 Logo Mounting Bracket 656-062 Outer Base Cover Black 656-017F...
  • Page 77 Fireglass Starfire 6mm / 454g Pkg 946-596 Heatwave Duct Kit 946-780 Crushed Glass Coal Black 19 mm / 1.6 kg 946-710 Stones -Slate/Grey Basalt Natural 6.8 kgs 946-711 Stones - Ivory/Tan Basalt Natural 6.8 kgs May not be exactly as shown City Series ACC40E |...
  • Page 78: Warranty

    FPI Fireplace Products International Ltd. (“the manufacturer”) through its wholly owned subsidiary, Fireplace Products Australia Pty Ltd (for Australia and New Zealand customers) and sold under the Regency® brand of fireplace products (collectively referred to herein as “FPI”), extends this Limited Lifetime Warranty to the original purchaser of this appliance provided the product remains in the original place of installation.
  • Page 79 Limited Lifetime Warranty. Revision Date: December 2016 Regency Gas Products Warranty City Series ACC40E |...
  • Page 80 FPI may void this warranty. INCORRECT INSTALLATION OR GAS PRESSURE SETTINGS ARE NOT COVERED BY WARRANTY. A SERVICE OR CALLOUT FEE WILL BE CHARGED IN THESE CIRCUMSTANCES. Revision Date: December 2016 Regency Gas Products Warranty | City Series ACC40E...
  • Page 81 (including negligence), statute or otherwise. (b) Loss means any expense, cost or damage of any kind and includes Consequential Loss and a fine or penalty imposed by a statutory or other authority. Revision Date: December 2016 Regency Gas Products Warranty City Series ACC40E |...
  • Page 82 Product Registration and Customer Support: Thank you for choosing a Regency Fireplace. Regency strives to be a world leader in the design, manufacture, and marketing of hearth products. To provide the best support for your product, we request that you complete a product registration form found on our Web Site under Customer Care within ninety (90) days of purchase.
  • Page 83 City Series ACC40E |...
  • Page 84 Installer: Please complete the following information Dealer Name & Address: ____________________________________ ________________________________________________________ Installer: _________________________________________________ Phone #: ________________________________________________ Date Installed: ____________________________________________ Serial No.: _______________________________________________ © Copyright 2019, FPI Fireplace Products International Ltd. All rights reserved.

Table of Contents