FLUEING INTRODUCTION

The GF1500L uses the "balanced flue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner
draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room
air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and flue system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel
or gas burning appliance. Each direct vent gas appliance must use it's own separate flue system. Common flue systems are prohibited.

FLUEING ARRANGEMENT FOR HORIZONTAL TERMINATIONS

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
Note: Must use optional rigid pipe adapter (Part# 770-994) when using Simpson Dura Vent Only.
6.5
6.0
FLUE RESTRICTOR SETTING:
Flue restrictor factory set at Set 0.
Refer to the "Flue Restrictor Position" section for details on how to change the flue restrictor from the factory setting of Set 0 to Set 1 if required.
Maintain clearances to combustibles as listed in "Clearances" section
Horizontal flue must be supported every 0.9m
A flue guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Flex system can only be used up to 3m - otherwise rigid system must be used.
10 | Greenfire GF1500L-2
Meters
Restrictor Set #2
41 mm-open
Restrictor Set #1
44 mm-Open
1061 mm
Minimum
Height
Requirement
Restrictor Set #0
Full Open
(two 45
elbows equal one 90
o
o
elbow).