Venting Introduction; Venting Arrangement For Horizontal Terminations - Regency CC40LE-NG Owners & Installation Manual

City series zero clearance direct vent gas fireplace
Table of Contents

Advertisement

installation

Venting Introduction

The CC40LE/CC40RE uses the "balanced flue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer
liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room
air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or
gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.

Venting Arrangement for Horizontal Terminations

The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90
Note: When using rigid vent pie systems, the rigid pipe adapter (Part# 510-994) must be used in all applications.
VENT RESTRICTOR SETTING:
Vent restrictor factory set at Set 0.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 2 if required.
NOTE: A minimum of 1' (305mm) vertical off the top of the unit is required before any horizontal runs can start.
Note: For horizontal terminations the Regency Direct Vent Flex System may be used for installations with a maximum continuous
vent length of up to 10 feet. If longer runs are required, rigid pipe must be used.
Maintain clearances to combustibles as listed in "Clearances" section
Horizontal vent must be supported every 3 feet.
Firestops are required at each floor level and whenever passing through a wall.
A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Flex system can only be used up to 10 feet - otherwise rigid venting must be used.
| City Series
32
56-1/4" (1429mm)
(two 45
elbows equal one 90
o
o
elbow).