Clearances CC40LE/CC40RE

The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and vent system be installed only in accordance with these instructions.
Note: CC40LE shown in illustration. Clearances will be the same for the CC40RE.
Clearance: single sided
A: Mantel Height (min.)
B: Opening Height
C: From Floor
D: Sidewall (on one side)
E: Mantel Depth (Max.)
F: Alcove Depth
G: Convection Air Outlet
H: Convection Air Outlet Opening Offset
I: Chase Enclosure (Min.)
Hearth
See mantel clearances chart in this manual.
**
I
D
Dimension
**
15-1/16" (382mm)
Min. 0"
Min. 36" (914mm)
**
Min. 36" (914mm)
*
0-3" (76mm)
63" (1600mm)
0"
F
H
G
E
A
B
C
F
CC40 UNIT
Top View
Measured From:
Top of Fireplace Opening
Bottom/Top of Fireplace Opening
Bottom of Fireplace Opening
Side of Fireplace Opening
Front of Fireplace Opening
Front of Fireplace Opening
Top of Enclosure
Max. offset from top of chase enclosure
From Base of Unit
No hearth required
D
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may NOT be
recessed into combustible construction.
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
Alcove
Flue Clearances to Combustibles
Horizontal - Top
Horizontal - Side
Horizontal - Bottom
Vertical
Passing through wall/
floor/ceiling - when
firestop is used.
*
A minimum of 120 square
inches of open area, not
lower than 3" from top of
enclosure, required for all
installations
The HeatWave Duct Kit has differ-
ent clearance and framing require-
ments, check the HeatWave manual
for details.
Caution Requirements
WARNING
Fire hazard is an extreme risk
installation
3"
2"
2"
2"
1-1/2"
City Series |
13