Error code in STATUS parame-
ter (hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
E1
21
DF
80
E1
22
DF
80
E1
23
DF
80
E1
24
DF
80
E1
25
DF
80
E1
26
DF
80
E1
27
DF
80
E1
28
DF
80
E1
29
DF
80
E1
2A
DF
80
E1
2B
DF
80
E1
2C
DF
80
E1
2D
DF
80
E1
2E
DF
80
E1
3A
Only for "Counting" operating mode
1
Only for "Position input for technology object "Motion Control"" operating mode
2
Only for "Fast Mode" operating mode
3
Technology Module TM Count 1x24V (6ES7138-6AA00-0BA0)
Manual, 02/2017, A5E33002339-AB
Meaning
1
Low counting limit > comparison value 0
•
Low counting limit > comparison value 1
•
1
High counting limit > comparison value 0
•
High counting limit > comparison value 1
•
"Start value" parameter invalid
•
"Low counting limit" parameter invalid
•
"Start value" parameter invalid
•
"High counting limit" parameter invalid
•
"Update time" parameter invalid
"Reference speed" parameter invalid
2
"Measured variable" parameter invalid
"Time base for velocity measurement" parame-
ter invalid
"Increments per unit" parameter invalid
"High counting limit" parameter invalid
•
"Low counting limit" parameter invalid
•
"Comparison value 0" parameter invalid
•
"Comparison value 1" parameter invalid
•
"Signal evaluation" parameter invalid
"Between comparison value 0 and 1" con-
•
figured for DQn.0
"Not between comparison value 0 and 1"
•
configured for DQn.0
"Between comparison value 0 and 1" con-
•
figured for DQn.1, but "Use by user pro-
gram" not configured for DQn.0
"Not between comparison value 0 and 1"
•
configured for DQn.1, but "Use by user pro-
gram" not configured for DQn.0
"Capture" configured for DIn.m in "Measuring"
operating mode
"Count direction for synchronization" parameter
3
invalid
Parameter data record
A.2 Parameter validation error
Remedy
Low counting limit < comparison value 0
•
Low counting limit < comparison value 1
•
High counting limit < comparison value 0
•
High counting limit < comparison value 1
•
Enter valid parameter value:
Start value > low counting limit
Enter valid parameter value:
Start value < high counting limit
Enter parameter value from range 0 to 25000000
Enter parameter value from range 6.00 to
210000.00
.
D
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value:
Low counting limit < high counting limit
Enter valid parameter value:
Comparison value 0 < comparison value 1
Enter valid parameter value.
Configure "Between comparison value 0 and 1"
•
only for DQn.1
Configure "Not between comparison value 0 and
•
1" only for DQn.1
Only configure "Between comparison value
•
0 and 1" for DQn.1, when "Use by user program"
is configured for DQn.0
Only configure "Not between comparison value
•
0 and 1" for DQn.1, when "Use by user program"
is configured for DQn.0
Do not configure "Capture" for DIn.m in "Measuring"
operating mode.
Enter valid parameter value.
.
D
83