Siemens SIMATIC ET 200SP Manual page 79

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Bit →
Bit 7
Byte ↓
10...15
10
Set output (DQ1):
0000
: Digital output without function
B
0001
: Between comparison value and high limit
B
0010
: Between comparison value and low limit
B
0011
: At comparison value for a pulse duration
B
0100
: Between comparison value 0 and 1
B
0101 to 1111
: Invalid
B
11
Count direction (DQ1):
00
: Reserved
B
01
: Up
B
10
: Down
B
11
: In both directions
B
12
13
14
15
16
16
Reserved
Edge selection (DI0):
2)
00
01
10
11
17
18
19
Frequency:
Count direction for syn-
chronization
0
: Once
00
B
1
: Periodic
01
B
10
11
Technology Module TM Count 1x24V (6ES7138-6AA00-0BA0)
Manual, 02/2017, A5E33002339-AB
A.1 Parameter assignment and structure of the parameter data record
Bit 6
Bit 5
Count direction (DQ0):
00
: Reserved
B
01
: Up
B
10
: Down
B
11
: In both directions
B
UINT: Value range in ms/10: 0 to 65535
UINT: Value range in ms/10: 0 to 65535
: Invalid
B
: At rising edge
B
: At falling edge
B
: Invalid
B
: Invalid
B
: Up
B
: Down
B
: In both directions
B
Bit 4
Bit 3
Behavior of a DQ
Set output (DQ0):
0000
: Digital output without function
B
0001
: Between comparison value and high limit
B
0010
: Between comparison value and low limit
B
0011
: At comparison value for a pulse duration
B
0100
to 1111
B
Reserved
2)
Pulse duration (DQ0):
Pulse duration (DQ1):
Behavior of DI0
Select level
Reserved
2)
(DI0):
0
: Active
B
with high
level
1
: Active
B
with low
level
Behavior of DI1:
See Byte 16
Behavior of DI2:
See Byte 16
Reserved
Input delay:
2)
0000
: None
B
0001
: 0.05 ms
B
0010
: 0.1 ms
B
0011
: 0.4 ms
B
0100
: 0.8 ms
B
0101
: 1.6 ms
B
0110
: 3.2 ms
B
0111
: 12.8 ms
B
1000
: 20 ms
B
1001 to 1111
Parameter data record
Bit 2
Bit 1
: Invalid
B
Reserved
Substitute
2)
value for
DQ1
D
D
Set function of DI (DI0):
000
: Gate start/stop (level-triggered)
B
001
: Gate start (edge-triggered)
B
010
: Gate stop (edge-triggered)
B
011
: Synchronization
3)
B
100
: Enable synchronization at signal N
B
101
: Invalid
B
110
: Digital input without function
B
111
: Invalid
B
: Invalid
B
Bit 0
Substitute
value for
DQ0
79

Advertisement

Table of Contents
loading

Table of Contents