Siemens SIMATIC ET 200SP Manual page 74

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter data record
A.1 Parameter assignment and structure of the parameter data record
Bit →
Bit 7
Byte ↓
4...51
4
4
Reserved
2)
5
5
Reserved
2)
6...7
6
Sensor type:
00
: Sourcing output
B
01
: Sinking output
B
10
: Push-pull (sinking
B
and sourcing output)
11
: Invalid
B
7
Reaction to signal N:
00
: No reaction to sig-
B
nal N
01
: Synchronization at
B
signal N
10
: Capture at signal N
B
11
: Invalid
B
74
Bit 6
Bit 5
Signal evaluation:
00
: Single
B
01
: Double
B
10
: Quadruple
B
11
: Invalid
B
Invert direc-
Enable
tion
diagnostics
1)
interrupt at
wire break
Bit 4
Bit 3
Counting channel
Operating mode
Operating mode:
0000
: Reserved
B
0001
: Counting
B
0010
: Measuring
B
0011 to 1111
: Invalid
B
Basic parameters
Enable
additional
diagnostic
interrupts
Counter inputs
Signal type:
0000
: Pulse (A)
B
0001
: Pulse (A) and direction (B)
B
0010
: Count up (A), count down (B)
B
0011
: Incremental encoder (A, B phase-shifted)
B
0100
: Incremental encoder (A, B, N)
B
0101 to 1111
: Invalid
B
Filter frequency:
0000
: 100 Hz
B
0001
: 200 Hz
B
1)
0010
: 500 Hz
B
0011
: 1 kHz
B
0100
: 2 kHz
B
0101
: 5 kHz
B
0110
: 10 kHz
B
0111
: 20 kHz
B
1000
: 50 kHz
B
1001
: 100 kHz
B
1010
: 200 kHz
B
1011 to 1111
: Invalid
B
Technology Module TM Count 1x24V (6ES7138-6AA00-0BA0)
Bit 2
Bit 1
Reaction to CPU STOP:
00
: Output substitute
B
value
1)
01
: Keep last value
B
10
: Continue operation
B
11
: Invalid
B
Manual, 02/2017, A5E33002339-AB
Bit 0

Advertisement

Table of Contents
loading

Table of Contents