3.7 Control Circuit Wiring
When connecting control wires to the terminals, use shielded twisted-pair wires (treating wire ends as shown in
Figure 3.16
and connect the shield to the ground terminal of the drive.
Figure 3.17
NOTICE: Do not exceed 50 meters (164 ft.) for the control line between the drive and the operator when using an analog signal from a
remote source to supply the frequency reference. Failure to comply could result in poor system performance.
u Switches and Jumpers on the Terminal Board
The terminal board is equipped with a jumper used to adapt the drive I/Os to the external control signals.
shows the location of this jumper. Refer to
Figure 3.18
58
A
B
A – Drive side
B – Connect shield to ground
terminal of drive.
C – Insulation
Figure 3.16 Preparing the Ends of Shielded Cables
Control I/O Configuration on page 59
Jumper CN1
Figure 3.17 Jumper CN1 Location on Terminal Board
YASKAWA EUROPE SIEP
F
C
D
E
D – Control device side
E – Shield sheath (insulate with
tape or heat-shrink tubing)
F – Shield
CN1
AM AC RP AC
S7 HC SC H1 PC P1
S1
S2 S3 S4 S5 S6
MD
for setting instructions.
ME
MF
MA MB
MC