4.8 Verifying Parameter Settings and Backing Up Changes

4.8

Verifying Parameter Settings and Backing Up Changes

Use the Verify Menu to check all changes to parameter settings as a result of Auto-Tuning.
Changes: Verify Menu on page
Save the verified parameter settings. Change the access level or set a password to the drive to prevent accidental
modification of parameter settings.
u Backing Up Parameter Values: o2-03
Setting o2-03 to 1 saves all parameter settings before resetting o2-03 to 0. The drive can now recall all the saved
parameters by performing a User Initialization (A1-03 = 1110).
No.
Parameter Name
User Parameter
o2-03
Default Value
A1-03
Initialize Parameters
u Parameter Access Level: A1-01
Setting the Access Level for "Operation only" (A1-01 = 0) allows the user to access parameters A1-
only. Other parameters are not displayed.
Setting the Access Level for "User Parameters" (A1-01 = 1) allows the user to access only the parameters that have been
previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific
application.
Parameter
No.
Name
Selects which parameters are accessible via the digital operator.
0: Operation only. A1-01, A1-04, and A1-06 can be set and monitored, and U -
Access Level
A1-01
1: User Parameters. Only recently changed parameters from application parameters A2-01 to A2-16 and A2-17 to A2-32
Selection
can be set and monitored.
2: Advanced Access Level. All parameters can be set and monitored.
Parameters selected by the user are saved as User Parameters, including recently viewed parameters and parameters
specifically selected for quick access.
A2-01
User Parameters
If parameter A2-33 is set to 1, recently viewed parameters will be listed between A2-17 and A2-32. Parameters A2-01
to
1 to 32
through A2-16 must be manually selected by the user.
A2-32
If A2-33 is set to 0, recently viewed parameters will not be saved to the group of User Parameters. A2-
are now available for manual programming.
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.
User Parameter
1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-17 through A2-32 for
A2-33
Automatic Selec-
quick access. The most recently changed parameter is saved to A2-17. The second most recently changed parameter is
tion
saved to A2-18.
u Password Settings: A1-04, A1-05
The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to
unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following
parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01,
A1-02, A1-03 and A2-01 through A2-33.
Note: Parameter A1-05 is hidden from view. To display A1-05, access parameter A1-04 and press
98
73.
Lets the user create a set of default settings for a User Initialization.
0: Saved/Not Set
1: Set Defaults - Saves current parameter settings as the default values for a User Initialization.
2: Clear All - Clears the currently saved user settings. After saving the user parameter set value, the items of
1110 (User Initialization) are displayed in A1-03 (User Parameter Default Value).
Selects a method to initialize the parameters.
0: No Initialize
1110: User Initialization (The user must first program and store desired settings using parameter o2-03)
2220: 2-Wire Initialization (parameter initialized prior to shipment)
5550: oPE4 Fault reset
YASKAWA EUROPE SIEP
Description
Description
parameters can also be viewed.
Refer to Verifying Parameter
Setting Range Default Setting
0 to 2
0 to 2220, 5550
and U -
Setting
Range
0 to 2
A1-00 to
o4-13
parameters
0, 1
and
simultaneously.
YASKAWA AC Drive L1000V Technical Manual
0
0
Default
2
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents