Capacitor Bank Overvoltage Settings (Read/Write, Grouped Setting); Capacitor Bank Overvoltage Actuals (Read Only) (3 Modules); Negative Sequence Instantaneous Overcurrent - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
Capacitor Bank Overvoltage Settings (Read/Write, Grouped Setting) (3 Modules)
C70
6330
Bank Phase Overvoltage 1 Function
"
6331
Bank Phase Overvoltage 1 Bus Source
"
6332
Bank Phase Overvoltage 1 Neutral Source
"
6333
Bank Phase Overvoltage 1 Bank Ground
"
6334
Bank Phase Overvoltage 1 Curve
"
6335
Bank Phase Overvoltage 1 Curve Time
Multiplier
"
6336
Bank Phase Overvoltage 1 Stage 1A Pickup 0.8 to 2
"
6337
Bank Phase Overvoltage 1 Stage 2A Pickup 0.8 to 2
"
6338
Bank Phase Overvoltage 1 Stage 3A Pickup 0.8 to 2
"
6339
Bank Phase Overvoltage 1 Stage 4A Pickup 0.8 to 2
"
633A
Bank Phase Overvoltage 1 Stage 1B Pickup 0.8 to 2
"
633B
Bank Phase Overvoltage 1 Stage 2B Pickup 0.8 to 2
"
633C
Bank Phase Overvoltage 1 Stage 3B Pickup 0.8 to 2
"
633D
Bank Phase Overvoltage 1 Stage 4B Pickup 0.8 to 2
"
633E
Bank Phase Overvoltage 1 Stage 1C Pickup 0.8 to 2
"
633F
Bank Phase Overvoltage 1 Stage 2C Pickup 0.8 to 2
"
6340
Bank Phase Overvoltage 1 Stage 3C Pickup 0.8 to 2
"
6341
Bank Phase Overvoltage 1 Stage 4C Pickup 0.8 to 2
"
6342
Bank Phase Overvoltage 1 Stage 1 Pickup
Delay
"
6343
Bank Phase Overvoltage 1 Stage 2 Pickup
Delay
"
6344
Bank Phase Overvoltage 1 Stage 3 Pickup
Delay
"
6345
Bank Phase Overvoltage 1 Dropout Delay
"
6346
Bank Phase Overvoltage 1 Block
"
6348
Bank Phase Overvoltage 1 Target
"
6349
Bank Phase Overvoltage 1 Events
"
634A
...Repeated for Bank Phase Overvoltage 2
"
6364
...Repeated for Bank Phase Overvoltage 3

Capacitor Bank Overvoltage Actuals (Read Only) (3 Modules)

C70
6390
Bank Overvoltage 1 Phase A Operate
Voltage
"
6391
Bank Overvoltage 1 Phase B Operate
Voltage
"
6392
Bank Overvoltage 1 Phase C Operate
Voltage
"
6393
...Repeated for Bank Overvoltage 2
"
6396
...Repeated for Bank Overvoltage 3
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 Modules)
C70, D30, D60,
63C0
Negative Sequence Instantaneous OC 1
F35, F60, L30,
Function
L60, L90
"
63C1
Negative Sequence Instantaneous OC 1
Signal Source
"
63C2
Negative Sequence Instantaneous
Overcurrent 1 Pickup
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
0 to 5
---
1
0 to 5
---
1
0 to 2
---
1
0 to 3
---
1
1 to 10
---
0.01
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
pu
0.001 F001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 65.535
pu
0.001 F001
0 to 65.535
pu
0.001 F001
0 to 65.535
pu
0.001 F001
0 to 1
---
1
0 to 5
---
1
0 to 30
pu
0.001 F001
MEMORY MAP
Format
Default
F102
0 (Disabled)
F167
0 (SRC 1)
F167
0 (SRC 1)
F093
0 (Grounded)
F094
0 (FlexCurve
A)
F001
100
1050
1100
1200
1050
1050
1100
1200
1050
1050
1100
1200
1050
F001
6000
F001
1000
F001
200
F001
25
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
0
0
0
F102
0 (Disabled)
F167
0 (SRC 1)
1000
2-75
2

Hide quick links: