B90 Power System (Read/Write Setting); Transformer General (Read/Write Setting); Transformer Windings (Read/Write Settings) (6 Modules); Incipient Cable Fault Detector (Read/Write Settings) (2 Or 6 Modules) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
461B
Block GPS Time Reference
"
461D
Maximum Channel Asymmetry
"
461F
Round Trip Time

B90 Power System (Read/Write Setting)

B90
4627
Terminal Nominal Frequency
"
4628
Terminal Reference
"
462F
Terminal Frequency Tracking Function

Transformer General (Read/Write Setting)

G30, T35, T60
4630
Transformer Number of Windings
"
4631
Transformer Phase Compensation
"
4632
Transformer Load Loss at Rated Load
"
4633
Transformer Rated Winding Temperature
Rise
"
4634
Transformer No Load Loss
"
4635
Transformer Type of Cooling
"
4636
Transformer Top-oil Rise Over Ambient
"
4637
Transformer Thermal Capacity
"
4638
Transformer Winding Thermal Time
Constant
"
4639
Transformer Reference Winding Manual
Selection

Transformer Windings (Read/Write Settings) (6 Modules)

G30, T35, T60
4640
Transformer Winding 1 Source
"
4641
Transformer Winding 1 Rated MVA
"
4643
Transformer Winding 1 Nominal Phase-
Phase Voltage
"
4645
Transformer Winding 1 Connection
"
4646
Transformer Winding 1 Grounding
"
4647
Transformer Winding 1 Angle w.r.t. Winding
1
"
4651
Transformer Winding 1 Resistance
"
4653
...Repeated for Transformer Winding 2
"
4666
...Repeated for Transformer Winding 3
"
4679
...Repeated for Transformer Winding 4
"
468C
...Repeated for Transformer Winding 5
"
469F
...Repeated for Transformer Winding 6

Incipient Cable Fault Detector (Read/Write Settings) (2 or 6 Modules)

F35, F60
46B2
Incipient Cable Fault Detector 1 Function
"
46B3
Incipient Cable Fault Detector 1 Block
"
46B5
Incipient Cable Fault Detector 1 Source
"
46B6
Incipient Cable Fault Detector 1 Pickup
"
46B7
Incipient Cable Fault Detector 1 Mode
"
46B8
Incipient Cable Fault Detector 1 Counts
"
46B9
Incipient Cable Fault Detector 1 Time
Window
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 4294967295
---
1
0 to 10
ms
0.1
0 to 10
ms
0.1
25 to 60
Hz
1
0 to 23
---
1
0 to 1
---
1
2 to 6
---
1
0 to 1
---
1
1 to 20000
kW
1
0 to 4
---
1
1 to 20000
kW
1
0 to 6
---
1
1 to 200
°C
1
0 to 200
kWh/°C 0.01
0.25 to 15
min
0.01
0 to 7
---
1
0 to 5
---
1
0.001 to 2000
MVA
0.001 F003
0.001 to 2000
kV
0.001 F003
0 to 2
---
1
0 to 1
---
1
-359.9 to 0
degrees 0.1
0.0001 to 100
ohms
0.000
1
0 to 1
---
1
0 to 4294967295
---
1
0 to 5
---
1
0.1 to 10
pu
0.01
0 to 1
---
1
1 to 10
---
1
0 to 1000
s
0.01
MEMORY MAP
Format
Default
F300
0
F001
15
F001
15
F001
60
F400
0
F102
1 (Enabled)
F001
2
F160
0 (Internal
(software))
F001
100
F161
1 (65°C (oil))
F001
10
F162
0 (OA)
F001
35
F001
10000
F001
200
F470
0
(Auto. Selecti
on)
F167
0 (SRC 1)
100000
220000
F163
0 (Wye)
F164
0 (Not within
zone)
F002
0
F003
100000
F102
0 (Disabled)
F300
0
F167
0 (SRC 1)
F001
50
F254
0 (Number of
Counts)
F001
2
F003
1000
2-57