Restricted Ground Fault (Read/Write Grouped Setting) (4 Or 6 Modules); Iec 61850 Received Analog Settings (Read/Write) (32 Modules) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
A90D
Frequency Rate of Change 1 OV
Supervision
"
A90E
Frequency Rate of Change 1 Reserved (3
items)
"
A911
...Repeated for Frequency Rate of Change 2
"
A922
...Repeated for Frequency Rate of Change 3
"
A933
...Repeated for Frequency Rate of Change 4

Restricted Ground Fault (Read/Write Grouped Setting) (4 or 6 Modules)

F60, G30, G60,
A960
Restricted Ground Fault 1 Function
L90, T60
"
A961
Restricted Ground Fault 1 Source
"
A962
Restricted Ground Fault 1 Pickup
"
A963
Restricted Ground Fault 1 Slope
"
A964
Restricted Ground Fault 1 Delay
"
A965
Restricted Ground Fault 1 Reset Delay
"
A966
Restricted Ground Fault 1 Block
"
A968
Restricted Ground Fault 1 Target
"
A969
Restricted Ground Fault 1 Events
"
A96A
...Repeated for Restricted Ground Fault 2
"
A974
...Repeated for Restricted Ground Fault 3
"
A97E
...Repeated for Restricted Ground Fault 4
F60, G60, L90,
A988
...Repeated for Restricted Ground Fault 5
T60
"
A992
...Repeated for Restricted Ground Fault 6

IEC 61850 Received Analog Settings (Read/Write) (32 Modules)

All
AA00
IEC 61850 GOOSE Analog 1 Default Value
"
AA02
IEC 61850 GOOSE Analog Input 1 Mode
"
AA03
IEC 61850 GOOSE Analog Input 1 Units
"
AA05
IEC 61850 GOOSE Analog Input 1 Per-Unit
Base
"
AA07
...Repeated for IEC 61850 GOOSE Analog
Input 2
"
AA0E
...Repeated for IEC 61850 GOOSE Analog
Input 3
"
AA15
...Repeated for IEC 61850 GOOSE Analog
Input 4
"
AA1C
...Repeated for IEC 61850 GOOSE Analog
Input 5
"
AA23
...Repeated for IEC 61850 GOOSE Analog
Input 6
"
AA2A
...Repeated for IEC 61850 GOOSE Analog
Input 7
"
AA31
...Repeated for IEC 61850 GOOSE Analog
Input 8
"
AA38
...Repeated for IEC 61850 GOOSE Analog
Input 9
"
AA3F
...Repeated for IEC 61850 GOOSE Analog
Input 10
"
AA46
...Repeated for IEC 61850 GOOSE Analog
Input 11
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0.1 to 3
pu
0.001 F001
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0.005 to 30
pu
0.001 F001
0 to 100
%
1
0 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
–1000000 to
---
0.001 F060
1000000
0 to 1
---
1
---
---
---
0 to 999999999.999 ---
0.001 F060
MEMORY MAP
Format
Default
700
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
80
F001
40
F001
0
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
1000
F491
0 (Default
Value)
F207
(none)
1
2-135
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents