CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
Setting Groups (Read Only)
All except C30
5F7F
Current Setting Group

Setting Group Names (Read/Write Setting)

All except C30
5F8C
Setting Group 1 Name
"
5F94
Setting Group 2 Name
"
5F9C
Setting Group 3 Name
"
5FA4
Setting Group 4 Name
"
5FAC
Setting Group 5 Name
"
5FB4
Setting Group 6 Name

Current Differential 87L (Read/Write Grouped Setting)

L30, L90
6000
87L Current Differential Function
"
6001
87L Current Differential Block
"
6003
87L Current Differential Signal Source 1
"
6004
87L Minimum Phase Current Sensitivity
"
6005
87L Current Differential Tap Setting
"
6006
87L Current Differential Phase Percent
Restraint 1
"
6007
87L Current Differential Phase Percent
Restraint 2
"
6008
87L Current Differential Phase Dual Slope
Breakpoint
"
6009
87L Current Differential Ground Function
"
600A
87L Current Differential Ground Pickup
"
600B
87L Current Differential Ground Restraint
"
600C
87L Current Differential Ground Delay
"
600D
87L Current Differential Key DTT
"
600E
87L Current Differential External Key DTT
"
6010
87L Current Differential Target
"
6011
87L Current Differential Event
"
6012
87L Current Differential Tap 2 Setting
L90
6013
87L Current Differential Signal Source 2
"
6014
87L Current Differential Signal Source 3
"
6015
87L Current Differential Signal Source 4
Current Differential 87L In-Zone Transformer (Read/Write Grouped Setting)
L30, L90
601E
87L Inrush Inhibit Mode
"
601F
87L Inrush Inhibit Level

Open Pole Detect (Read/Write Grouped Setting)

C60, N60
6040
Open Pole Detect Function
"
6041
Open Pole Detect Block
"
6043
Open Pole Detect A Aux Co
"
6045
Open Pole Detect B Aux Co
"
6047
Open Pole Detect C Aux Co
"
6049
Open Pole Detect Current Source
"
604A
Open Pole Detect Current Pickup
"
604B
Open Pole Detect Voltage Source
"
604C
Open Pole Detect Voltage Input
"
604D
Open Pole Detect Pickup Delay
"
604E
Open Pole Detect Reset Delay
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 5
---
1
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0 to 1
---
1
0 to 4294967295
---
1
0 to 5
---
1
0.1 to 4
pu
0.01
0.2 to 5
---
0.01
1 to 50
%
1
1 to 70
%
1
0 to 20
pu
0.1
0 to 1
---
1
0.05 to 1
pu
0.01
1 to 50
%
1
0 to 5
seconds 0.01
0 to 1
---
1
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0.2 to 5
---
0.01
0 to 6
---
1
0 to 6
---
1
0 to 6
---
1
0 to 3
---
1
1 to 40
%fo
0.1
0 to 1
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 4294967295
---
1
0 to 5
---
1
0.05 to 20
pu
0.01
0 to 5
---
1
0 to 1
---
1
0 to 65.535
s
0.001 F001
0 to 65.535
s
0.001 F001
MEMORY MAP
Format
Default
F001
0
F203
(none)
F203
(none)
F203
(none)
F203
(none)
F203
(none)
F203
(none)
F102
0 (Disabled)
F300
0
F167
0 (SRC 1)
F001
20
F001
100
F001
30
F001
50
F001
10
F102
0 (Disabled)
F001
10
F001
25
F001
10
F102
1 (Enabled)
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
100
F211
0 (None)
F211
0 (None)
F211
0 (None)
F561
0 (Disabled)
F001
200
F102
0 (Disabled)
F300
0
F300
0
F300
0
F300
0
F167
0 (SRC 1)
F001
20
F167
0 (SRC 1)
F102
0 (Disabled)
60