CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name
"
58D0
...Repeated for FlexLogic Timer 27
"
58D8
...Repeated for FlexLogic Timer 28
"
58E0
...Repeated for FlexLogic Timer 29
"
58E8
...Repeated for FlexLogic Timer 30
"
58F0
...Repeated for FlexLogic Timer 31
"
58F8
...Repeated for FlexLogic Timer 32
Phase Time Overcurrent (Read/Write Grouped Setting (1, 2, 4, or 6 Modules)
B30, C60, C70,
5900
Phase Time Overcurrent 1 Function
D30, D60, F35,
F60, G30, G60,
L30, L60, L90,
T35, T60
"
5901
Phase Time Overcurrent 1 Signal Source
"
5902
Phase Time Overcurrent 1 Input
"
5903
Phase Time Overcurrent 1 Pickup
"
5904
Phase Time Overcurrent 1 Curve
"
5905
Phase Time Overcurrent 1 Multiplier
"
5906
Phase Time Overcurrent 1 Reset
"
5907
Phase Time Overcurrent 1 Voltage
Restraint
"
5908
Phase TOC 1 Block For Each Phase (3 items) 0 to 4294967295
"
590F
Phase Time Overcurrent 1 Target
"
5910
Phase Time Overcurrent 1 Events
"
5911
Reserved (3 items)
B30, C60, C70,
5914
...Repeated for Phase Time Overcurrent 2
D30, D60, F35,
F60, L30, L60,
L90, T35, T60
B30, C60, C70,
5928
...Repeated for Phase Time Overcurrent 3
D60, F35, F60,
L60, L90, T35,
T60
"
593C
...Repeated for Phase Time Overcurrent 4
B30, C60, C70,
5950
...Repeated for Phase Time Overcurrent 5
F35, L90, T35,
T60
"
5964
...Repeated for Phase Time Overcurrent 6
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (2, 4, 6, 8, or 12 Modules)
All except B90,
5A00
Phase Instantaneous Overcurrent 1
C30, T35
Function
"
5A01
Phase Instantaneous Overcurrent 1 Signal
Source
"
5A02
Phase Instantaneous Overcurrent 1 Pickup 0 to 30
"
5A03
Phase Instantaneous Overcurrent 1 Delay
"
5A04
Phase Instantaneous Overcurrent 1 Reset
Delay
"
5A05
Phase IOC1 Block For Each Phase (3 items) 0 to 4294967295
"
5A0B
Phase Instantaneous Overcurrent 1 Target 0 to 2
"
5A0C
Phase Instantaneous Overcurrent 1 Events 0 to 1
"
5A0D
Reserved (6 items)
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 1
---
1
0 to 5
---
1
0 to 1
---
1
0 to 30
pu
0.001 F001
0 to 16
---
1
0 to 600
---
0.01
0 to 1
---
1
0 to 1
---
1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
pu
0.001 F001
0 to 600
s
0.01
0 to 600
s
0.01
---
1
---
1
---
1
0 to 1
---
1
MEMORY MAP
Format
Default
F102
0 (Disabled)
F167
0 (SRC 1)
F122
0 (Phasor)
1000
F103
0 (IEEE Mod
Inv)
F001
100
F104
0
(Instantaneo
us)
F102
0 (Disabled)
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
1000
F001
0
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
2-63