Auxiliary Overvoltage (Read/Write Grouped Setting) (3 Modules); Requency (Read Only); Generic Comparator Settings (Read/Write Setting) (6 Modules); Generic Comparator Actual Values (Read Only) (6 Modules) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

MEMORY MAP
Products
Address Register name
"
7F66
"
7F68
"
7F69
"
7F6A
"
7F71
"
7F82
2

Auxiliary Overvoltage (Read/Write Grouped Setting) (3 Modules)

All except B90,
7FA0
C30, N60, T35
"
7FA1
"
7FA2
"
7FA3
"
7FA4
"
7FA5
"
7FA7
"
7FA8
"
7FA9
"
7FB1
"
7FC2
Frequency (Read Only)
All except B90,
8000
C30

Generic Comparator Settings (Read/Write Setting) (6 Modules)

N60
8010
"
8011
"
8013
"
8014
"
8016
"
8017
"
8018
"
8028
"
8029
"
802A
"
802C
"
802E
"
802F
"
8030
"
8040
"
8044
"
8078
"
80AC
"
80E0
"
8114

Generic Comparator Actual Values (Read Only) (6 Modules)

N60
8150
"
8152
"
8154
2-110
Auxiliary Undervoltage 1 Block
Auxiliary Undervoltage 1 Target
Auxiliary Undervoltage 1 Events
Reserved (7 items)
...Repeated for Auxiliary Undervoltage 2
...Repeated for Auxiliary Undervoltage 3
Auxiliary Overvoltage 1 Function
Auxiliary Overvoltage 1 Signal Source
Auxiliary Overvoltage 1 Pickup
Auxiliary Overvoltage 1 Pickup Delay
Auxiliary Overvoltage 1 Reset Delay
Auxiliary Overvoltage 1 Block
Auxiliary Overvoltage 1 Target
Auxiliary Overvoltage 1 Events
Reserved (8 items)
...Repeated for Auxiliary Overvoltage 2
...Repeated for Auxiliary Overvoltage 3
Tracking Frequency
Comparator 1 Function
Comparator 1 Addition/Subtraction Mode
Operand
Comparator 1 Scale Factor
Comparator 1 Block
Comparator 1 Target
Comparator 1 Events
Comparator 1 Argument A Bits (8 items)
Comparator 1 Input Mode
Comparator 1 Direction Mode
Comparator 1 Pickup
Comparator 1 Hysteresis
Comparator 1 Pickup Delay
Comparator 1 Reset Delay
Comparator 1 Argument B Bits (8 items)
Reserved (4 items)
...Repeated for Comparator 2
...Repeated for Comparator 3
...Repeated for Comparator 4
...Repeated for Comparator 5
...Repeated for Comparator 6
Comparator 1 Argument A Value
Comparator 1 Argument B Value
Comparator 1 Output Value
CHAPTER 2: MODBUS COMMUNICATION
Range
Units
Step
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 1
---
1
0 to 5
---
1
0 to 3
pu
0.001 F001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
2 to 90
Hz
0.01
0 to 1
---
1
0 to 4294967295
---
1
0.01 to 100
---
0.01
0 to 4294967295
---
1
0 to 2
---
1
0 to 1
---
1
0 to 4294967295
---
1
0 to 1
---
1
0 to 1
---
1
-25400 to 25400
---
0.01
0 to 5000
---
0.01
0 to 65.353
s
0.001 F001
0 to 65.353
s
0.001 F001
0 to 4294967295
---
1
0 to 65535
---
1
-12700 to 12700
---
0.01
-12700 to 12700
---
0.01
-25400 to 25400
---
0.01
UR SERIES – COMMUNICATIONS GUIDE
Format
Default
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
300
F001
100
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F001
0
F102
0 (Disabled)
F300
0
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F300
0
F515
0 (SIGNED)
F517
0 (OVER)
F004
1000000
F003
50000
0
0
F300
0
F001
0
F004
0
F004
0
F004
0