Field Unit Process Card Ports (Read/Write Setting); Field Unit Ct Vt Settings (Read/Write Setting) (6 Modules); Field Unit Contact Inputs (Read/Write Setting) (40 Modules) - GE UR Series Manual

Hide thumbs Also See for UR Series:
Table of Contents

Advertisement

CHAPTER 2: MODBUS COMMUNICATION
Products
Address Register name

Field Unit Process Card Ports (Read/Write Setting)

All except B90,
3878
Field Unit 1 Process Card Port
L60
"
3879
Field Unit 2 Process Card Port
"
387A
Field Unit3 Process Card Port
"
387B
Field Unit 4 Process Card Port
"
387C
Field Unit 5 Process Card Port
"
387D
Field Unit 6 Process Card Port
"
387E
Field Unit 7 Process Card Port
"
387F
Field Unit 8 Process Card Port

Field Unit CT VT Settings (Read/Write Setting) (6 Modules)

All except B90,
3890
Remote Phase CT x Origin 1
L60
"
3891
Remote Phase CT x Origin 2
"
3892
Remote Ground CT x Origin 1
"
3893
Remote Ground CT x Origin 2
"
3894
AC Bank Redundancy Type
"
3895
Remote Phase CT 1 Primary
"
3896
Remote Phase CT 1 Secondary
"
3897
Remote Ground CT 1 Primary
"
3898
Remote Ground CT 1 Secondary
"
3899
Remote Phase VT 1 Connection
"
389A
Remote Phase VT 1 Secondary
"
389B
Remote Phase VT 1 Ratio
"
389D
Remote Auxiliary VT 1 Connection
"
389E
Remote Auxiliary VT 1 Secondary
"
389F
Remote Auxiliary VT 1 Ratio
"
38A1
...Repeated for Field Unit 2
"
38B2
...Repeated for Field Unit 3
"
38C3
...Repeated for Field Unit 4
"
38D4
...Repeated for Field Unit 5
"
38E5
...Repeated for Field Unit 6

Field Unit Contact Inputs (Read/Write Setting) (40 Modules)

All except B90,
3900
Field Contact Input 1 ID
L60
"
3906
Field Contact Input 1 Origin
"
3907
Field Contact Input 1 Input
"
3908
Field Contact Input 1 Failsafe Value
"
3909
Field Contact Input 1 Debounce Time
"
390A
Field Contact Input 1 Events
"
390B
...Repeated for Field Contact Input 2
"
3916
...Repeated for Field Contact Input 3
"
3921
...Repeated for Field Contact Input 4
"
392C
...Repeated for Field Contact Input 5
"
3937
...Repeated for Field Contact Input 6
"
3942
...Repeated for Field Contact Input 7
UR SERIES – COMMUNICATIONS GUIDE
Range
Units
Step
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 7
---
1
0 to 16
---
1
0 to 16
---
1
0 to 16
---
1
0 to 16
---
1
0 to 2
---
1
1 to 65000
---
1
0 to 1
---
1
1 to 65000
---
1
0 to 1
---
1
0 to 1
---
1
25 to 240
---
0.1
1 to 24000
---
1
0 to 6
---
1
25 to 240
---
0.1
1 to 24000
---
1
---
---
---
0 to 8
---
1
1 to 18
---
1
0 to 1
---
1
0 to 16
ms
0.5
0 to 1
---
1
MEMORY MAP
Format
Default
F244
6 (H1a)
F244
4 (H2a)
F244
2 (H3a)
F244
0 (H4a)
F244
7 (H1b)
F244
5 (H2b)
F244
3 (H3b)
F244
1 (H4b)
F247
0 (None)
F247
0 (None)
F248
0 (None))
F248
0 (None)
F261
1
(Dependabili
ty Biased)
F001
1
F123
0 (1 A)
F001
1
F123
0 (1 A)
F100
0 (Wye)
F001
664
F060
1
F166
1 (Vag)
F001
664
F060
1
F205
"FCI 1"
F256
0 (None)
F001
1
F108
0 (Off)
F001
60
F102
1 (Enabled)
2-45
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents