Commonly used parameters
Table 2- 1
Switching to commissioning mode or restore the factory setting
Parameter
Description
p0010
Commissioning parameters
0: Ready (factory setting)
1: Perform quick commissioning
3: Perform motor commissioning
5: Technological applications and units
15: Define number of data records
30: Factory setting - initiate restore factory settings
Table 2- 2
How to determine the firmware version of the Control Unit
Parameter
Description
r0018
The firmware version is displayed:
Table 2- 3
How you select the command source and setpoint sources
Parameter
Description
p0015
Parameter p0015 allows the setting of pre-defined I/O configurations. Further information is given in the
section: Selecting the interface assignments (Page 41).
Table 2- 4
This is how you parameterize the up and down ramps
Parameter
Description
p1080
Minimum speed
0.00 [rpm] factory setting
p1082
Maximum speed
1500.000 [rpm] factory setting
p1120
Rampup time
10.00 [s]
p1121
Rampdown time
10.00 [s]
16