Table 11- 11 Technical specifications of the line reactors
Feature
MLFB
MLFB of the suitable
inverter
Inductance
Power loss at 50/60 Hz
Cross section
Tightening torque
PE connection
Degree of protection
Overall dimensions
Width
Height
Depth
Fixing dimensions
Width
Height
Fixing screw
Weight
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
11.0 kW ... 18.5 kW
FSC
6SL3203-0CE23-8AA0
6SL3210-1KE22-6 ⃞ ⃞ 0
6SL3210-1KE23-2 ⃞ ⃞ 0
6SL3210-1KE23-8 ⃞ ⃞ 0
0.3 mH
90 W
16 mm
/ 5 AWG
2
2 Nm ...4 Nm
18 lbf in ... 35 lbf in
M5 (5 Nm / 44 lbf in)
IP20
180 mm
220 mm
118.5 mm
136 mm
99.5 mm
4 × M6 (10 Nm)
7.8 kg
Suitable for inverter with rated power of
Technical data