Functions
8.10 Fail-safe function Safe Torque Off (STO)
8.10.8.5
Function test
Table 8- 42
"Safe Torque Off" (STO) function
No.
1.
Initial state:
The inverter is in "Ready" state (p0010 = 0).
•
The inverter indicates neither faults nor alarms for safety functions (r0945, r2122, r2132).
•
STO is not active.
•
2.
Switch on the motor (ON command).
3.
Ensure that the correct motor is running.
4.
Select STO while the motor is running
Note: Test each configured activation, e.g. via digital inputs and PROFIsafe.
5.
Check the following:
If a mechanical brake is not available, the motor coasts down.
•
A mechanical brake brakes the motor and holds it to ensure that it remains at a standstill.
The inverter indicates neither faults nor alarms for safety functions.
•
The inverter indicates:
•
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
6.
Deselect STO.
7.
Check the following:
The inverter indicates neither faults nor alarms for safety functions.
•
The inverter indicates:
•
"STO is not selected" (r9773.0 = 0).
"STO is not active" (r9773.1 = 0).
The inverter is in "Closing lockout" state (p0046.0 = 1).
•
8.
Switch the motor off (OFF1 command) and then on again (ON command).
9.
Ensure that the correct motor is running.