Technical data

11.1

Technical data of inputs and outputs

Feature
Output voltages
Setpoint resolution
Digital inputs
Analog input (differential
input, resolution 12 bits)
Digital outputs / relay
outputs
Analog output
Temperature sensor
Fail-safe Input
PFH
USB-interface
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
Data
24 V (max. 100 mA)
10 V ± 0.5 V (max. 10 mA)
0.01 Hz
6 digital inputs, DI 0 ... DI 5, isolated;
Low < 5 V, high > 11 V, maximum input voltage 30 V, current consumption 5.5 mA
Response time: 5.5 ms ± 1 ms
AI0: configurable as additional digital inputs
0 V ... 10 V, 0 mA ... 20 mA and -10 V ... +10 V,
Low < 1.6 V, High > 4.0 V
Response time: 10 ms ± 2 ms
DO 0: relay output, 30 V DC / max. 0.5 A with resistive load
DO 1: transistor output, 30 V DC / max. 0.5 A with resistive load, protection against
incorrect voltage polarity
Update time of all DO: 2 ms
AO 0: 0 V ... 10 V or 0 mA ... 20 mA, reference potential: "GND", resolution 16 bit, update
time: 4 ms
PTC: Short-circuit monitoring 22 Ω, switching threshold 1650 Ω
KTY84
ThermoClick sensor with dry contact
DI4 and DI5 are combined to form a single fail-safe input
Maximum input voltage 30 V, 5.5 mA
Response time:
Typical: 6 ms + debounce time (p9651)
Worst-case scenario: 10 ms + debounce time (p9651)
5 × 10E-8
Mini-B
11
273