8.4.4

Running the motor in jog mode (JOG function)

Using the "jog" function (JOG function), you can switch the motor on and off using a control
command or the operator panel. The speed to which the motor accelerates for "Jog" can be
set.
The motor must be switched-off before you issue the "jog" control command. "Jog" has no
effect when the motor is switched on.
The "Jog" function is typically used to manually switch-on a motor after switching over from
automatic to manual operation.
Setting jogging
The "Jog" function has two different speed setpoints, e.g. for motor counter-clockwise
rotation and clockwise rotation.
With an operator panel, you can always select the "Jog" function. If you wish to use
additional digital inputs as control commands, you must interconnect the particular signal
source with a digital input.
Table 8- 19
Parameter
p1055
p1056
p1058
p1059
SINAMICS G120C Inverter
Operating Instructions, 01/2011, FW 4.4, A5E02999804A AB
Parameters for the "Jog" function
Description
Signal source for jogging 1 - jog bit 0 (factory setting: 0)
If you wish to jog via a digital input, then set p1055 = 722.x
Signal source for jogging 2 - jog bit 1 (factory setting: 0)
If you wish to jog via a digital input, then set p1056 = 722.x
Jogging 1 speed setpoint (factory setting, 150 rpm)
Jogging 2 speed setpoint (factory setting, 150 rpm)
Functions
8.4 Setpoint sources
179