2.
Determine secondary power requirement at the –48-V output
power requirements of the boards/
components used =
+
power requirement of connected work-
point clients, key modules and adapt-
ers =
=
secondary power requirement at the –
48-V output =
The maximum nominal output of UPSC-D at the –48-V output amounts to 53 W and is
enough to cover the specified power requirement.
P31003-H3560-S403-54-7620, 09/05
HiPath 3000 V6.0, HiPath 5000 V6.0, Provisional Service Manual
Checking Whether the Output of a Power Supply Unit is Sufficient
Identifying System Power Requirements
0.50 W
1 x CBCC
2.80 W
1 x HXGS3 (including ventilator
kit)
0.00 W
1 x TS2
0.00 W
3 x SLU8
1.30 W
1 x 8SLA
0.00 W
1 x SLC16N
24.00 W
12 x BS3/1
0.56 W
1 x optiset E memory
4.32 W
6 x optiPoint 500 advance
0.85 W
1 x optiset E advance confer-
ence/conference
8.40 W
12 x optiPoint 500 basic
2.40 W
8 x optiPoint 500 entry
0.00 W
2 x Hicom Attendant BLF
0.00 W
2 x optiPoint BLF
0.40 W
8 x optiPoint key module
0.50 W
2 x optiPoint acoustic adapter
1.80 W
6 x analog telephones
47.83 W