YASKAWA A1000 Quick Start Manual page 46

Frequency high performance vector control ac drive
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

9 UL Standards
Input Fuse Installation
The installation manual specifies that branch circuit protection should be provided by fuses listed in the table below.
Model
CIMR-A
2A0004
2A0006
2A0010
2A0012
2A0021
2A0030
2A0040
2A0056
2A0069
2A0081
2A0110
2A0138
2A0169
2A0211
2A0250
2A0312
2A0360
2A0415
4A0002
4A0004
4A0005
4A0007
4A0009
4A0011
4A0018
4A0023
4A0031
4A0038
4A0044
4A0058
4A0072
4A0088
4A0103
4A0139
4A0165
4A0208
4A0250
4A0296
4A0362
4A0414
4A0515
4A0675
4A0930
4A1200
Note: Model CIMR-A 4A1200 is UL compliant when the air entering the drive-installed panel or cabinet is 45
information, contact your nearest Yaskawa representative or our sales office.
46
Manufacturer: Bussmann
Model
Three-Phase 200 V Class
FWH-70B
FWH-70B
FWH-70B
FWH-70B
FWH-90B
FWH-100B
FWH-200B
FWH-200B
FWH-200B
FWH-300A
FWH-300A
FWH-350A
FWH-400A
FWH-400A
FWH-600A
FWH-700A
FWH-800A
FWH-1000A
Three-Phase 400 V Class
FWH-40B
FWH-50B
FWH-70B
FWH-70B
FWH-90B
FWH-90B
FWH-80B
FWH-100B
FWH-125B
FWH-200B
FWH-250A
FWH-250A
FWH-250A
FWH-250A
FWH-250A
FWH-350A
FWH-400A
FWH-500A
FWH-600A
FWH-700A
FWH-800A
FWH-800A
FWH-1000A
FWH-1200A
FWH-1200A
FWH-1600A
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Fuse Type
Fuse Ampere Rating (A)
70
70
70
70
90
100
200
200
200
300
300
350
400
400
600
700
800
1000
40
50
70
70
90
90
80
100
125
200
250
250
250
250
250
350
400
500
600
700
800
800
1000
1200
1200
1600
°
C or less. For more

Advertisement

Table of Contents
loading

Table of Contents