Wiring Specification
Main Circuit
Use the fuses and line filters listed in the table below when wiring the main circuit. Make sure not to exceed the given
tightening torque values.
Model
EMC Filter
CIMR-A
[Schaffner]
2A0004
FS5972-10-07
2A0006
2A0010
FS5972-18-07
2A0012
2A0021
FS5972-35-07
2A0030
2A0040
FS5972-60-07
2A0056
2A0069
FS5972-100-35
2A0081
2A0110
FS5972-170-40
2A0138
2A0169
FS5972-250-37
2A0211
2A0250
FS5972-410-99
2A0312
2A0360
FS5972-600-99
2A0415
4A0002
4A0004
FS5972-10-07
4A0005
4A0007
4A0009
FS5972-18-07
4A0011
4A0018
4A0023
FS5972-35-07
4A0031
4A0038
4A0044
FS5972-60-07
4A0058
4A0072
FS5972-100-35
4A0088
4A0103
4A0139
FS5972-170-40
4A0165
4A0208
FS5972-250-37
4A0250
4A0296
FS5972-410-99
4A0362
4A0414
FS5972-600-99
4A0515
4A0675
FS5972-800-99
4A0930
FS5972-600-99
4A1200
FS5972-800-99
<1> Connect two of the same filters in parallel. Refer to the Technical Manual for details.
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
Main Fuse
[Bussmann]
FWH-70B
FWH-90B
FWH-100B
FWH-200B
FWH-300A
FWH-350A
FWH-400A
FWH-600A
FWH-700A
FWH-800A
FWH-1000A
FWH-40B
FWH-50B
FWH-70B
FWH-90B
FWH-80B
FWH-100B
FWH-125B
FWH-200B
FWH-250A
FWH-350A
FWH-400A
FWH-500A
FWH-600A
FWH-700A
FWH-800A
FWH-800A
FWH-1000A
FWH-1200A
FWH-1200A
<1>
FWH-1600A
<1>
Recom.
R/L1,S/L2,T/L3,
Motor cable
U/T1,V/T2,W/T3,
(mm
2
)
– , +1, +2
2.5
M4
6
10
M6
16
25
M8
35
50
70
M10
95
95 × 2P
M12
240
300
2.5
M4
4
6
M5
M6
16
25
M8
35
50
70
M10
95
120
185
240
95 × 2P
150 × 2P
M12
95 × 4P
120 × 4P
(95 × 4P) × 2
3 Electrical Installation
Main Circuit Terminal Sizes
+3
B1, B2
M4
M5
M8
M10
M10
M4
M5
M8
M10
M12
M4
M5
M6
M8
M12
M4
M5
M6
M8
M10
M12
13