YASKAWA A1000 Quick Start Manual page 44

Frequency high performance vector control ac drive
Hide thumbs Also See for A1000:
Table of Contents

Advertisement

9 UL Standards
Model
Terminal
CIMR-A
R/L1, S/L2, T/L3,
R1/L11, S1/L21,
T1/L31
U/T1, V/T2, W/
4A1200
T3
<4>
–, +1
+3
<1> Gauges listed here are for use in Europe and China.
<2> Gauges listed here are for use in the United States.
<3> Gauges listed here are for use in Asia except for China.
<4> Drive models CIMR-A 4A0058 to 4A1200 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
Note: 1. Model CIMR-A 4A1200 is UL compliant when the air entering the drive-installed panel or cabinet is 45°C or less. For more
information, contact your nearest Yaskawa representative or our sales office.
2. Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum allowable
temperature of 75°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.
44
For Europe and
China
<1>
Recommen
Applicable
ded Gauge
Gauge
mm
2
mm
2
(95 × 4P) × 2
95 to 150
(95 × 4P) × 2
95 to 150
120 to 150
95 to 150
95 × 4P
95 to 120
For U.S.A
<2>
Recommen
Applicable
ded Gauge
Gauge
AWG, kcmil
AWG, kcmil
(300 × 4P) × 2
4/0 to 300
(300 × 4P) × 2
4/0 to 300
250 to 300 (150 × 4P) × 2 125 to 150
4/0 to 300
4/0
4/0 to 250
YASKAWA ELECTRIC TOEP C710616 27D YASKAWA AC Drive - A1000 Quick Start Guide
For Asia
<3>
Recommen
Applicable
ded Gauge
Gauge
mm
2
mm
2
(125 × 4P) × 2 100 to 150
(125 × 4P) × 2 100 to 150
(100 × 4P) × 2 100 to 150
125
100 to 125
Tightening
Screw
Torque
Size
N m (lb.in.)
32 to 40
M12
(283 to 354)