Figure 111 Binding the cables
Route, bind, and attach excess cables for easy, safe maintenance activities and correct
operations.
Do not tie the power cables to the slide rails.
When you connect a cable to an articulated part, for example, when you connect a grounding
cable to a cabinet door, leave enough slack in cables and make sure they are not stressed from
any movement of the part.
Cables must be protected at points where they might rub or come in contact with sharp edges or
heated areas. Use high temperature cables near heat sources.
Securely fasten cables and take adequate measures to prevent loose connections.
Figure 112 Securely fastening cables
(1) (1)(2)
(1) (1)(2)
(1) Flat washer
Fasten heavy or rigid power cables at the connectors to relief stress.
Do not use tapping screws to fasten the connecting terminals.
Bind together cables that are the same type and routed in the same direction.
Table 76
lists the cable bundling specifications.
Table 76 Cable bundling specifications
Cable bundle diameter (mm)
10
10 to 30
30
(3)
(3)
(2) Spring washer
Space between bundles (mm)
80 to 150
150 to 200
200 to 300
135