Refrigerant Tubing Connection And Evacuation; Refrigerant Flow-Control Device; Ground Connections; Minimum Cfm And Motor Speed Selection - Carrier fb4cnf024 Installation Instructions Manual

Table of Contents

Advertisement

D.Ground C onnections
ELECTRICALSHOCK
HAZARD
Failure
to follow
this warning
could result in personal
iniury
or death.
According
to NEC,
ANSI/NFPA
70, and local
codes,
the
cabinet
must
have an uninterrupted
or unbroken
ground
to
minimize
personal
iniury
if an electrical
fault should
occur.
The ground
may consist
of electrical
wire
or metal conduit
when
installed
in accordance
with existing
electrical
codes. If
conduit
connection
uses reducing
washers,
a separate
ground
wire must be used.
NOTE:
Use
UL-listed
conduit
and
conduit
connector
for
connecting
supply
wire(s)
to unit
to obtain
proper
grounding.
Grounding
may
also be accomplished
by using
grounding
lugs
provided
in control
box.
E. Minimum
CFM
and Motor
Speed
Selection
Units
with or without
electric
heaters
require
a minimum
CFM.
Refer to the unit wiring
label to ensure
that the fan speed selected
is
not lower than the minimum
fan speed indicated.
FY5B
fan speed selection
is done
at the fan relay printed-circuit
board. To change
motor speeds,
disconnect
fan lead used on relay
terminal
(SPT) and replace with motor speed tap desired.
(See Fig.
17.) Save insulating
cap and place
on motor
lead removed
from
relay.
NOTE:
In low static applications,
lower
motor speed tap should
be used to reduce possibility
of water being
blown
off coil.
FY5B
have 2 motor speed
taps. Low speed (red)
and high speed
(black).
The 060 size only will have a Medium
speed (blue).
See Table 2 - FY5B Airflow
Performance
(CFM),
for each setting.
INSULATING
CAP
(2)
MOTOR
8
A97529
Fig. 17 - Fan
Coil Relay and
Speed Tap Terminal
for FY5B
Models
The fan speed selection
on the FB4C
models
is done at the motor.
Units
with or without
electric
heaters
require
a minimum
CFM.
Refer to the unit wiring
label to ensure
that the fan speed selected
is
not lower than the minimum
fan speed indicated.
To change
motor
speeds
disconnect
the BLUE
fan lead from
terminal
#2 (factory
default
position)
and move
to desired
speed-tap;
1, 2, 3, or 5.
Speed-taps
1, 2, and 3 have
a 90 second
blower
time
delay
pre-programmed
into the motor.
Speed
tap 4 is used for electric
heat only (with 0 second
blower
time delay)
and the WHITE
wire
must
remain
on
tap
4.
Speed-tap
5 is used
for
high
static
applications,
but
has
a
0
second
blower
time
delay
pre-programmed
into
the motor
(see Table
1 - FB4C
Airflow
Performance
(CFM),
for each tap setting.
Also,
see Fig.
18 for
motor speed selection
location.
NOTE:
In low static applications,
lower motor
speed tap should
be used to reduce possibility
of water being blown
off coil.
F
Fig. 18 - Motor
Speed
Selection
A09390
Step 5 -- Refrigerant
Tubing
Connection
and
Evacuation
Use
accessory
tubing
package
or
field-supplied
tubing
of
refrigerant
grade.
Suction
tube
must
be
insulated.
Do
not use
damaged,
dirty,
or contaminated
tubing
because
it may
plug
refrigerant
flow-control
device.
ALWAYS
evacuate
the coil and
field-supplied
tubing
to 500 microns
before opening
outdoor
unit
service valves.
PRODUCT
DAMAGE
HAZARD
Failure
to follow
this caution
may
result
in
product
or
property
damage.
A brazing
shield MUST
be used when
tubing
sets are being
brazed to the unit connections
to prevent
damage
to the unit
surface
and condensate
pan fitting caps.
Units
have
sweat
suction
and
liquid
tube
connections.
Make
suction
tube connection
first.
1. Cut tubing to correct length.
2. Insert tube into sweat connection
on unit until it bottoms.
3. Braze connection
using silver bearing
or non-silver
bearing
brazing
materials.
Do not use solder (materials
which
melt
below
800°F
/ 427°C).
Consult
local code requirements.
4. Evacuate
coil and tubing
system to 500 microns
using deep
vacuum
method.
PRODUCT
DAMAGE
HAZARD
Failure
to follow
this caution
may
result
in
product
or
property
damage.
Wrap a wet cloth around
rear of fitting
to prevent
damage
to
piston
assembly
or TXV
and factory-made
joints.
Step 6 -- Refrigerant
Flow-Control
Device
FB4C
units
come
equipped
with
a factory
installed
Piston
with
Teflon
ring
metering
device
(sizes
018
thru
060).
If a piston
replacement
if required,
check
piston
size shown
on indoor
unit

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fb4cFy5bFb4cnf030

Table of Contents