Carrier FAS072 Installation, Start-Up And Service Instructions Manual
Carrier FAS072 Installation, Start-Up And Service Instructions Manual

Carrier FAS072 Installation, Start-Up And Service Instructions Manual

Packaged air-handling units with r-410a refrigerant

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . 2
Moving and Storage . . . . . . . . . . . . . . . . . . . . . . 2
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . 12
Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant Piping Access . . . . . . . . . . . . . . . . 13
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . 17
Fan Motors and Drives . . . . . . . . . . . . . . . . . . . 17
Power Supply and Wiring . . . . . . . . . . . . . . . . 17
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . 22
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . 22
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Adjusting TXV for Superheat . . . . . . . . . . . . . . 24
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Motor Lubrication . . . . . . . . . . . . . . . . . . . 24
Fan Shaft Bearings . . . . . . . . . . . . . . . . . . . . . . 24
Centering Fan Wheel . . . . . . . . . . . . . . . . . . . . 25
Fan Shaft Position Adjustment . . . . . . . . . . . . 25
Individual Fan Wheel Adjustment . . . . . . . . . . 25
Fan Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fan Pulley Alignment . . . . . . . . . . . . . . . . . . . . 26
Pulley and Drive Adjustment . . . . . . . . . . . . . . 26
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . 26
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . 26
Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . 26
Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . 26
Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . 37
START-UP CHECKLIST . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical
FAS/FHS 072-180
Packaged Air-Handling Units
with R-410A Refrigerant
Installation, Start-up and
Service Instructions
Page
FAS-FHS-072-180-01SI Rev. A
components. Only trained and qualified service personnel
should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service
personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may
apply.
Follow all safety codes, including ANSI (American National
Standards Institute) Z223.1. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguisher available for all brazing operations.
It is important to recognize safety information. This is the
safety-alert symbol
. When you see this symbol on the
unit and in instructions or manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal
injury or death. CAUTION is used to identify unsafe
practices, which may result in minor personal injury or
product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation,
reliability, or operation.
DANGER
ELECTRICAL SHOCK HAZARD
Failure to follow this warning will result in personal injury
or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lock(s) and lockout tag(s). Ensure electrical service to
rooftop unit agrees with voltage and amperage listed on
the unit rating plate. Unit may have more than one
power switch.
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
R-410A refrigerant systems operate at higher pressures
than standard R-22 systems. Do not use R-22 service
equipment or components on R-410A refrigerant
equipment.
1-22

Advertisement

Table of Contents
loading

Summary of Contents for Carrier FAS072

  • Page 1: Table Of Contents

    FAS/FHS 072-180 Packaged Air-Handling Units with R-410A Refrigerant Installation, Start-up and Service Instructions components. Only trained and qualified service personnel CONTENTS should install, repair, or service air-conditioning equipment. Page Untrained personnel can perform basic maintenance SAFETY CONSIDERATIONS ....1 functions of cleaning coils and filters and replacing filters.
  • Page 2: Pre-Installation

    provincial and local plumbing or wastewater codes and other applicable local codes. WARNING Moving and Storage PERSONAL INJURY AND ENVIRONMENTAL To transfer unit from truck to storage site, use a fork truck. HAZARD Do not stack units more than 2 high during storage. If unit is Failure to follow this warning could cause personal injury to be stored for more than 2 weeks before installation, or death.
  • Page 3 A = Standard NOTES: 1. All FAS072-150 and FHS072-120 units with an “M” voltage designation are triple voltage, i.e., 208/230/460-3-60. 2. For both FAS and FHS models, “M” voltage is not available on 2-speed indoor fan motor options. 3. Single phase FAS072-091 and FHS072-091 units designate standard motor and high static drive.
  • Page 4 Fig. 2 — Dimensions – Sizes 072-120 FAS-FHS-072-180-01SI Rev. A Specifications subject to change without notice.
  • Page 5 Fig. 2 —Dimensions – Sizes 072-120 (cont) FAS-FHS-072-180-01SI Rev. A Specifications subject to change without notice.
  • Page 6 Fig. 3 — Dimensions – Size 150 and 180 FAS-FHS-072-180-01SI Rev. A Specifications subject to change without notice.
  • Page 7 Fig. 3 —Dimensions – Size 150 and 180 (cont) FAS-FHS-072-180-01SI Rev. A Specifications subject to change without notice.
  • Page 8 Table 1 — FAS Physical Data, English — Cooling Units FAS UNIT NOMINAL CAPACITY (tons) 7-1/2 12-1/2 OPERATING WEIGHT (lb) Base Unit with TXV Plenum FANS Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 Nominal Airflow (cfm) 2400 3000 4000 5000 6000 Airflow Range (cfm) 1800-3000...
  • Page 9 Table 2 — FAS Physical Data, SI — Cooling Units FAS UNIT NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) Base Unit with TXV Plenum FANS Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 Nominal Airflow (L/s) 1133 1604 1888 2360 2831 Airflow Range (L/s) 850-1416 1203-2006 1416-2360...
  • Page 10 Table 3 — FHS Physical Data, English — Heat Pump Units FHS UNIT 072****2 NOMINAL CAPACITY (tons) 7-1/2 OPERATING WEIGHT (lb) Base Unit with TXV Plenum FANS Qty...Diam. (in.) 1...15 1...15 1...15 1...15 2...15 Nominal Airflow (cfm) 2400 2400 3000 4000 6000 Airflow Range (cfm)
  • Page 11 Table 4 — FHS Physical Data, SI — Heat Pump Units FHS UNIT 072****2 NOMINAL CAPACITY (kW) OPERATING WEIGHT (kg) Base Unit with TXV Plenum FANS Qty...Diam. (mm) 1...381 1...381 1...381 1...381 2...381 Nominal Airflow (L/s) 1133 1133 1604 1888 2831 Airflow Range (L/s) 850-1416...
  • Page 12: Rated Indoor Airflow (Cfm)

    Air Intake and Discharge Table 5 — CAS (1 Circuit) with FAS MODEL NUMBER FULL LOAD AIRFLOW (CFM) Fig. 5 — Typical Unit Positioning CAS072*A/B — FAS072 2400 CAS072*G/H — FAS072 2625 CAS091*A/B — FAS091 3000 IMPORTANT: Do NOT attempt to install unit with return air entering top panel of unit.
  • Page 13: Refrigerant Piping

    The standard knockouts 4 o’clock or 8 o’clock position. (See Fig. 10.) provide sufficient access to the unit’s coils for all FAS072, 091, 120, 150, and 180 and FHS072, 091, and 120 units. FAS-FHS-072-180-01SI Rev. A...
  • Page 14 FIELD-FABRICATED HOLE DIAMETERS FIELD-FABRICATED HOLE POSITION USE HOLE IN. (MM) DIMENSIONS, IN. (MM) UNIT NUMBERS NO. 5 NO. 6 NO.7 FAS072, 091 1, 3 — — — — — — FHS072,091 FAS120, 150, 180 1, 2, 3, 4 —...
  • Page 15 ACCESS HOLE NO.* CONNECTION TYPE CIRCUIT FITTING REQUIRED† (IN.) 1-1/8 Street Elbow Suction — 1-1/8 Nipple, 10-5/8 L 1-1/8 Long Radius Elbow FAS072 FHS072 5/8 Street Elbow Liquid — 5/8 Nipple, 8-5/8 L 5/8 Long Radius Elbow 1-1/8 Street Elbow Suction —...
  • Page 16 EQUALIZER LINE UPPER SENSING SPLIT BULB SOLENOID VALVE EQUALIZER LINE SIGHT AIRFLOW GLASS 15 DIAMS UPPER SENSING SPLIT BULB FILTER DIAMS SOLENOID DRIER 8 DIAMS VALVE SIGHT GLASS EQUALIZER AIRFLOW 15 DIAMS FILTER LINE DRIER SENSING LOWER DIAMS BULB SPLIT 8 DIAMS AIRFLOW 15 DIAMS...
  • Page 17: Condensate Drain

    1 — adjustable motor pulley 3” MIN. 1 — fan pulley [76] 1 — fan belt (FAS072-120, FHS072-120 units) 2 — matched fan belts (FAS150-180, FHS180 units) For instructions on changing fan rotation, changing drive speeds and adjusting drives, see “Pulley and Drive Adjust- ment”...
  • Page 18 POWER SUPPLY VOLTAGE UNIT V-PH-Hz* MINIMUM CIRCUIT LIMITS Hp (kW) MAX FUSE AMPS 208/230-160 187-253 1.3 (0.97) 208/230-3-60 187-253 2.4 (1.79) FAS072 FHS072 460-3-60 414-506 2.4 (1.79) 575-3-60 518-632 1.0 (0.75) 208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 208/230-3-60 187-253 2.4 (1.79)
  • Page 19 Table 12 — Electrical Data, Standard Motors — Two Speed FAN MOTOR POWER SUPPLY VOLTAGE UNIT V-PH-Hz* MINIMUM CIRCUIT LIMITS Hp (kW) MAX FUSE AMPS 208/230-3-60 187-253 2.4 (1.79) FAS072 460-3-60 414-506 2.4 (1.79) FHS072 575-3-60 518-632 2.4 (1.79) 208/230-3-60 187-253 2.4 (1.79) FAS091 460-3-60 414-506 2.4 (1.79)
  • Page 20 Legend and Notes for Tables 10-13 Example: Supply voltage is 230-3-60 LEGEND max voltage deviation from average voltage %Voltage = 100 x Imbalance: average voltage — Full Load Amps HACR — Heating, Air Conditioning, and Refrigeration AB = 394 v * Motors are designed for satisfactory operation within 10% of normal BC = 403 v voltage shown.
  • Page 21 Install disconnect switch and power wiring in accordance Fan motors are factory-installed on all units. Indoor-fan with all applicable local codes. See Fig. 13-15 and the unit contactors are located in the fan contactor box behind the label diagram. For units with motor sizes less than 5 Hp side access panel.
  • Page 22: Connecting Ductwork

    Fig. 16 — Unit Wiring conform to the discharge opening. (See Fig. 18.) After Connecting Ductwork flanges are installed, connect them to the supply duct using a canvas connection to prevent vibration. It is important that Figure 17 shows recommended duct connection to units this connection be properly fabricated to prevent high air with 2 fans.
  • Page 23 Fig. 17 — Typical Fan Discharge Connections for Multiple Fan Units Fig. 18 — Duct Flange Installation FAS-FHS-072-180-01SI Rev. A Specifications subject to change without notice.
  • Page 24: Start-Up

    START-UP Before starting unit, check the following and correct as INSTALLER / INSTALLATEUR necessary: TXV superheat must be checked at initial • Is unit solidly supported? unit start-up and adjusted if necessary. • Is fan adjusted for speed and pulley alignment? Superheat must be 10 - 15 deg F.
  • Page 25: Centering Fan Wheel

    Fig. 21 — Fan Shaft, Bearings, and Fan Wheel Fig. 22 — Fan Shaft Bearing (Typical) Individual Fan Wheel Adjustment Centering Fan Wheel Loosen the 2 locking bolts holding the fan wheel hub to shaft. (See Fig. 21.) Position fan wheel in center of the fan If fan and fan shaft assembly are not properly centered, blades may scrape against the blower side scroll plate or housing and tighten locking bolts.
  • Page 26: Fan Rotation

    Fan Rotation 4. If pulleys are not in correct alignment, loosen the motor holddown bolts and slide the motor axially until the Correct fan rotation with respect to fan outlet is shown in pulleys are aligned. Fig. 24. To reverse the direction of rotation of a 3-phase fan motor, 5.
  • Page 27 Table 16 — Fan Motor Data, FAS/FHS Standard Motor, Single Speed — English FAS/FHS FAS/FHS FAS/FHS FAS/FHS UNIT 208/230-1-60 Speed (rpm) 1725 1725 — — — — — — Frame (NEMA) — — — Shaft Dia (in.) — — — 208/230-3-60 and 460-3-60 Speed (rpm) 1750...
  • Page 28 Table 19 — Fan Motor Data, FAS/FHS Standard Motor, Single Speed — SI FAS/FHS FAS/FHS FAS/FHS FAS/FHS UNIT 208/230-1-60 Speed (r/s) 28.75 28.75 — — — Shaft kW 0.97 1.79 — — — Frame (NEMA) — — — Shaft Dia (mm) 15.9 15.9 —...
  • Page 29 Table 21 — Fan Motor Data, FAS Standard Motor, Two Speed — English UNIT FAS072 FAS091 FAS120 FAS150 FAS180 208/230-3-60 and 460-3-60 Speed (rpm) 1680 1680 1680 1735 1750 Frame (NEMA) 56HY 56HY 56HY 56HY 56HY Shaft Dia (in.) 575-3-60...
  • Page 30 Table 26 — Fan Motor Data, FHS Standard Motor, Two Speed — English UNIT FHS072 FHS091 FHS120 FHS180 208/230-3-60 and 460-3-60 Speed (rpm) 1680 1680 1680 1750 Frame (NEMA) 56HY 56HY 56HY 56HY Shaft Dia (in.) 575-3-60 Speed (rpm) 1680 1680 1665 1710...
  • Page 31 Table 31 — Standard Drive Data, 60 Hz — English FAS/FHS FAS/FHS FAS/FHS FAS/FHS UNIT MOTOR DRIVE Motor Pulley Pitch Diameter (in.) 2.4-3.4 2.8-3.8 3.4-4.4 2.8-3.8 2.8-3.8 Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (in.) Pulley Bore (in.) 1-7/16 1-7/16 Belt No.
  • Page 32 Table 33 — Standard Drive Data, 60 Hz — SI FAS/FHS FAS/FHS FAS/FHS FAS/FHS UNIT MOTOR DRIVE Motor Pulley Pitch Diameter (mm) 61.0-86.4 71.1-96.5 86.4-111.8 71.1-96.5 71.1-96.5 Pulley Factory Setting Full Turns Open FAN DRIVE Pulley Pitch Dia (mm) Pulley Bore (mm) 25.4 25.4 25.4...
  • Page 33 EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW UNIT (Cfm) 1800 0.21 0.26 0.37 0.49 0.63 0.77 0.92 2100 0.31 0.37 0.49 0.62 0.77 0.92 1.09 FAS072 2400 0.44 0.51 0.64 0.79 0.94 1.11 1.28 FHS072 2700 0.61 0.69 0.84 0.99 1.15 1.33 1.51 3000 0.81 0.90...
  • Page 34 1.23 1026 1.39 1074 1.55 1120 1.72 1164 1.90 2100 1.26 1.43 1048 1.61 1097 1.79 1143 1.97 1186 2.16 FAS072 2400 1.47 1017 1.66 1069 1.85 1118 2.05 1164 2.25 — — FHS072 1090 2.12 1138 2.33 1185 2.55 2700 1.71...
  • Page 35 12.11 0.47 13.29 0.57 14.36 0.69 7.84 0.23 8.64 0.27 10.03 0.36 11.31 0.46 12.52 0.57 13.65 0.69 14.71 0.81 FAS072 1130 8.73 0.33 9.46 0.38 10.75 0.48 11.91 0.59 13.01 0.70 14.07 0.83 15.08 0.96 FHS072 1270 9.63 0.45 10.31...
  • Page 36 17.10 1.03 17.90 1.16 18.66 1.28 19.39 1.41 15.69 0.94 16.61 1.07 17.47 1.20 18.28 1.33 19.04 1.47 19.77 1.61 FAS072 1130 16.04 1.09 16.95 1.23 17.81 1.38 18.63 1.53 19.40 1.67 — — FHS072 18.17 1.58 18.87 1.74 19.75 1.90...
  • Page 37: Replacing Filters

    Replacing Filters Filters can be removed and installed from either side of the unit. Install new filters in units that have one fan as follows: 1. Remove the side access panel (retain screws). 2. Remove the filter retainer clip (see Fig. 26). 3.
  • Page 38 © 2022 Carrier Lewisburg, TN 37091 USA Replaces: 50801160301 Specifications are subject to change without notice. FAS-FHS-072-180-01SI Rev. A...
  • Page 39: Start-Up Checklist

    START-UP CHECKLIST (SPLIT SYSTEMS WITH FAS/FHS UNITS) NOTE: To avoid injury to personnel and damage to equipment or prop- erty when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety con- siderations/information as outlined in preceding sections of this Instal- lation, Start-Up, and Service document.
  • Page 40 CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES: ARE THE SIGHT GLASSES SHOWING OIL LEVEL AT 1/8 to 1/3 FULL? (Y/N)_______________ NOTES: ________________________________________________________________________________________________ ________________________________________________________________________________________________ ________________________________________________________________________________________________ ________________________________________________________________________________________________ ________________________________________________________________________________________________ ________________________________________________________________________________________________ © 2022 Carrier Lewisburg, TN 37091 USA Replaces: 50801160301 CL-2 Specifications are subject to change without notice. 1-22 FAS-FHS-072-180-01SI Rev. A...