Condensate Drains - Carrier fb4cnf024 Installation Instructions Manual

Table of Contents

Advertisement

rating p late
t o see if it matches
required
piston
shown
on outdoor
unit rating
plate.
If it does not match,
replace
indoor
piston
with
piston shipped
with outdoor
unit. The piston shipped
with outdoor
unit is correct
for any approved
indoor
coil combination
(See Fig.
19). When
changing
piston,
use a back-up
wrench.
Hand
tighten
hex nut, then
tighten
with wrench
1/2 turn.
Do not exceed
30
ft-lbs.
NOTE:
The indoor
piston contains
a Teflon ring (or seal) which
is
used to seat against
the inside
of distributor
body,
and must
be
installed
properly
to ensure
proper
seating
in the
direction
for
cooling
operation.
FY5B units
also contain
a factory
installed
Piston
with Teflon ring
for sizes
018
thru
048
only.
The
FY5B-060
size units
come
equipped
with a Puron refrigerant
TXV.
Always
use
outdoor
units
designed
to match
indoor
fan coil
applications.
BRASS_
HEX NUT\
TEFLON SEAL
\
)_,
TEFLON
RiNG
PISTON
l
1
1
FLOW iN
COOLING
PISTON
RETAINER
BRASS
HEX BODY
STRAINER
[]NIT
OR PROPERTY
DAMAGE
HAZARD
Failure
to follow
this caution
may
result
in
product
or
property
damage.
The conversion
of the fan coil to downflow
requires
special
procedures
for the
condensate
drains
on both
A-coil
and
slope
units.
The
vertical
drains
have
an
overflow
hole
between
the primary
and secondary
drain holes. This hole is
plugged
for all applications
except
downflow,
but must be
used for downflow.
During
the conversion
process,
remove
the plastic cap covering
the vertical
drains only
and discard.
Remove
the plug
from
the overflow
hole and discard.
At
completion
of the downflow
installation,
caulk
around
the
vertical
pan fitting
to door joint
to retain
the low
air leak
performance
of the unit.
Units
are equipped
with primary
and secondary
3/4-in.
FPT drain
connections.
For proper
condensate
line installations
see Fig. 1, 2,
3, 5 and 6. To prevent
property
damage
and achieve
optimum
drainage
performance,
BOTH
primary
and secondary
drain lines
should
be installed
and include
properly-sized
condensate
traps.
(See
Fig.
20 and
21.)
Factory-approved
condensate
traps
are
available.
It is recommended
that
PVC
fittings
be used
on the
plastic
condensate
pan. Finger-tighten
plus
1-1/2
turns.
Do not
over-tighten.
Use pipe dope.
PROPERTY
DAMAGE
HAZARD
Failure
to follow
this caution
may
result
in
product
or
property
damage.
Shallow
running
traps
are inadequate
and DO NOT
allow
proper
condensate
drainage.
(See Fig. 22.)
A09677
Fig. 19 - Refrigerant
Flow - Control
Device
PRODUCT
OPERATION
HAZARD
Failure to follow this caution may result in improper product
operation.
If using
a TXV
in conjunction
with
a single-phase
reciprocating
compressor, a compressor start capacitor and
relay are required. Consult outdoor unit pre-sale literature for
start assist kit part number.
Step 7 -- Condensate
Drains
To connect
drains, the cap openings
must be removed.
Use a knife
to start the opening
near the tab and using
pliers,
pull the tab to
remove
the disk.
Clean the edge
of the opening
if necessary
and
install
the condensate
line. Finally
caulk
around
the lines where
they exit the fitting to retain the low leak rating of the unit.
UNiT
f
2" M[N
(51 ram)
Fig. 20 - Recommended
Condensate
Trap
A03002

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fb4cFy5bFb4cnf030

Table of Contents