Heater Packages; Installation; Check Equipment; Mount Unit - Carrier fb4cnf024 Installation Instructions Manual

Table of Contents

Advertisement

HEATER
PACKAGES
This
unit may
or may not be equipped
with
an electric
heater
package.
For units
not equipped
with
factory-installed
heat,
a
factory-approved,
field-installed,
UL
listed
heater
package
is
available
from your equipment
supplier.
See unit rating
plate for a
list
of factory-approved
heaters.
Heaters
that
are
not
factory
approved
could
cause damage
which
would
not be covered
under
the equipment
warranty.
If fan coil
contains
a factory-installed
heater package,
minimum
circuit
ampacity
(MCA)
and maximum
fuse/breaker
may
be
different
than
units
with
a same
size
field-installed
accessory
heater. The differences
is not an error and
is due to calculation
difference
per UL guidelines.
INSTALLATION
Step 1 -- Check
Equipment
Unpack
unit and move to final location.
Remove
carton taking
care
not
to
damage
unit.
Inspect
equipment
for
damage
prior
to
installation.
File
claim
with
shipping
company
if shipment
is
damaged
or incomplete.
Locate
unit
rating
plate
which
contains
proper
installation
information.
Check
rating
plate
to be
sure
unit
matches
job
specifications.
Step 2 -- Mount Unit
Unit can stand or lie on floor, or hang from ceiling
or wall. Allow
space for wiring,
piping,
and servicing
unit.
IMPORTANT:
When
unit
is installed
over
a finished
ceiling
and/or
living
area,
building
codes
may require
a field-supplied
secondary
condensate
pan to be installed
under
the entire
unit.
Some
localities
may
allow
as an alternative,
the
running
of a
separate,
secondary
condensate
line.
Consult
local
codes
for
additional
restrictions
or precautions.
A. Upflow
Installation
If return
air is to be ducted
through a floor,
set unit on floor over
opening
and use 1/8 to l/4-in
(3 to 6 mm) thick fireproof
resilient
gasket between
duct, unit, and floor.
Side return is a field option on slope coil models.
Cut opening
per
dimensions.
(See
Fig.
1.) A
field-supplied
bottom
closure
is
required.
018
048
21" (533
n'lm)
FRONT
SERVICE
060
060
24" (610ram)
CLEARANCE
o 1'1 12"(3O%m,
024
030
17"
432mm)
[
036
19" (483
mm)
A07565
Fig. 1 - Slope Coil []nit
in Upllow Application
B. Downflow
Installation
In this application,
field conversion
of the evaporator
is required
using
accessory
downflow
kit along with
an accessory
base
kit.
Use fireproof
resilient
gasket,
1/8 to l/4-in
(3 to 6 mm) thick,
between
duct, unit, and floor.
[]NIT
OR PROPERTY
DAMAGE
HAZARD
Failure to follow this caution
may result in product
or property
damage.
The conversion
of the fan coil to downflow
requires
special
procedures
for the condensate
drains on both A-coil
and slope
units.
The vertical
drains
have an overflow
hole between
the
primary
and secondary
drain holes.
This hole is plugged
for all
applications
except downflow,
but must be used for downflow.
During
the
conversion
process,
remove
the
plastic
cap
covering
the vertical drains only and discard.
Remove
the plug
from
the
overflow
hole
and discard.
At completion
of the
downflow
installation,
caulk around
the vertical
pan fitting
to
door joint to retain the low air leak performance
of the unit.
NOTE:
To convert
units
for downflow
applications,
refer
to
Installation
Instructions
supplied
with
kit for proper
installation.
For slope fan coils, use kit Part No. KFADC0201SLP.
For A-coils,
use kit Part No. KFADC0401ACL
Use fireproof
resilient
gasket,
1/8 to l/4-in
(3 to 6 mm) thick, between
duct, unit, and floor.
NOTE:
Gasket
kit number
KFAHD0101SLP
is also required
for
all downflow
applications
to maintain
low
air
leak/low
sweat
performance.
C. Horizontal
Installation
[]nits
must not be installed
with access panels facing
up or down.
All other units are factory
built for horizontal
left installation.
(See
Fig.
2 and 3.) When
suspending
unit from
ceiling,
dimples
in
casing
indicate
suitable
location
of screws
for mounting
metal
support
straps. (See Fig. 2.)
PROPERTY
DAMAGE
HAZARD
Failure
to follow
this caution
may result in product
or property
damage.
For optimum
condensate
drainage
performance
in horizontal
installations,
unit should be leveled
along its length
and width.
For horizontal
applications
having
high
return
static and humid
return
air, the Water
Management
Kit, KFAHC0125AAA,
may
need to be used to assist in water management.
@RIMARY
RAIN
HANGING
STRAPS
LOW
voFr
ENTRY
OPTIONS
o#
SECONDARY
DRAIN
018-048
21" (533 turn)
060 060
24" (610 ram)
FRONT
SERVICE
CLEARANCE
:ULL
FACE
OF UNIT)
175"(44
mm)
FILIERACCESS
CLEARANCE
A07566
Fig. 2 - Slope (;oil []nit in Horizontal
Left Application