Step 5 - Refrigerant Tubing Connection And Evacuation; Step 6 - - Refrigerant Flow- -Control Device - Carrier PF4MNB 019 Installation Instructions Manual

Direct expansion fan coil unit
Hide thumbs Also See for PF4MNB 019:
Table of Contents

Advertisement

When 2 stages are desired, cut W3 at the W2 wire nut, strip and
reconnect per the thermostat kit instruction. (See Fig. 12.) When 3
stages are desired, cut the W2 wire nut off and discard. Strip W2,
W3, and E and reconnect per thermostat kit instructions. (See Fig.
13.)
NOTE: When 3 stages are used or anytime the E terminal is not
tied to W2, the emergency heat relay, part of outdoor kit Part No.
KHAOT0201SEC must be used.
C. Manufactured Housing
In manufactured housing applications, the Code of Federal
Regulations, Title 24, Chapter XX, Part 3280.714 requires that
supplemental electric heat be locked out at outdoor temperatures
above 40_F (4_C), except for a heat pump defrost cycle. Refer to
Fig. 14 for typical low voltage wiring with outdoor thermostat.
D. Ground Connections
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
According to NEC, ANSI/NFPA 70, and local codes, the
cabinet must have an uninterrupted or unbroken ground to
minimize personal injury if an electrical fault should occur.
The ground may consist of electrical wire or metal conduit
when installed in accordance with existing electrical codes. If
conduit connection uses reducing washers, a separate ground
wire must be used.
NOTE:
Use UL- -listed conduit and conduit connector for
connecting supply wire(s) to unit to obtain proper grounding.
Grounding may also be accomplished by using grounding lugs
provided in control box.
E. Minimum CFM and Motor Speed Selection
The fan speed selection is done at the motor connector. Units with
or without electric heaters require a minimum CFM. Refer to the
unit wiring label to ensure that the fan speed selected is not lower
than the minimum fan speed indicated.
Tap 1
Low
Tap 2
Medium
Tap 3
High
Tap 4
Electric heat †
Tap 5
Max ‡
† electric heat airflow is same CFM as Tap 3, except 0 sec off delay
‡ high static applications, see airflow tables for max airflow
To change motor speeds disconnect the BLUE fan lead from motor
connector terminal #2 (factory default position) and move to
desired speed-tap; 1, 2, 3, or 5.
Speed-taps 1, 2, and 3 have a 90 second blower off time delay
pre-programmed into the motor. Speed-tap 4 is used for electric
heat only (with 0 second blower time delay) and the WHITE wire
should remain on tap 4.
Speed-tap 5 is used for high static
applications,
but
has
a
pre-programmed into the motor. See Airflow Performance tables
for actual CFM. Also, see Fig. 16 for motor speed selection
location.
NOTE: In low static applications, lower motor speed tap should
be used to reduce possibility of water being blown off coil.
90 sec off delay
90 sec off delay
90 sec off delay
0 sec off delay
0 sec off delay
0
second
blower
time
delay
1 2 3 4 5
Speed Taps may be located on motor,
or on plug close to motor.
1 2 3 4 5
Fig. 16 - - Motor Speed Selection
Step 5 — Refrigerant Tubing Connection and
Evacuation
Use accessory tubing package or field- -supplied tubing of
refrigerant grade. Suction tube must be insulated. Do not use
damaged, dirty, or contaminated tubing because it may plug
refrigerant flow- -control device. ALWAYS evacuate the coil and
field- -supplied tubing to 500 microns before opening outdoor unit
service valves.
CAUTION
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product or property
damage.
A brazing shield MUST be used when tubing sets are being
brazed to the unit connections to prevent damage to the unit
surface and condensate pan fitting caps.
Units have sweat suction and liquid tube connections. Make
suction tube connection first.
1. Cut tubing to correct length.
2. Insert tube into sweat connection on unit until it bottoms.
3. Braze connection using silver bearing or non- -silver bearing
brazing materials. Do not use solder (materials which melt
below 800_F / 427_C). Consult local code requirements.
4. Evacuate coil and tubing system to 500 microns using deep
vacuum method.
7
A11048

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents