Current Protection: Measured Ef (67G, 51G, 50G); Directional Control Of Measured Earth Fault Protection (67G) - Siemens 7SR224 Technical Manual

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

3.3

Current Protection: Measured EF (67G, 51G, 50G)

The earth current is measured directly via a dedicated current analogue input.
All measured earth fault elements have a common setting to measure either fundamental frequency RMS, True
RMS current or the derived sum current:
True RMS current: 51/50 Measurement = RMS
Fundamental Frequency RMS current: 51/50 Measurement = Fundamental
Additionally these elements can be selected to operate on a Fundamental Frequency current which is calculated
from the sum of the phase currents, i.e. a Derived quantity. This option should only be used when the fourth
current input is required for connection of a Core Balance Current Transformer to achieve very low earth fault
sensitivity using the 50/51SEF elements.
51/50 Measurement = Calculated

3.3.1 Directional Control of Measured Earth Fault Protection (67G)

The directional element produces forward and reverse outputs for use with measured earth fault elements. These
outputs can be mapped as controls to each shaped and instantaneous element.
If a protection element is set as non-directional then it will operate independently of the output of the directional
detector. However, if a protection element is programmed for forward directional mode then operation will occur
only for a fault lying within the forward operate zone. Conversely, if a protection element is programmed for
reverse directional mode then operation will occur only for a fault lying within the reverse operate zone. Typically
the forward direction is defined as being 'away' from the busbar or towards the protected zone.
The Characteristic angle is the phase angle by which the polarising voltage must be adjusted such that the
directional detector gives maximum sensitivity in the forward operate zone when the current is in phase with it.
The reverse operate zone is the mirror image of the forward zone.
The measured directional earth fault elements use zero phase sequence (ZPS) polarising.
Voltage polarisation is achieved for the earth-fault elements by comparison of the appropriate current with its
equivalent voltage:
I
~ V
0
0
The characteristic angle can be user programmed to any angle between -95° and +95° using the 67G Char
Angle setting. The voltage is the reference phasor (V
the forward and reverse zones.
The centre of the forward zone is set by (V
Angle for maximum sensitivity e.g.
For fault current of -15
sensitivity, OR
For fault current of -45
sensitivity.
Minimum Polarising Voltage
The 67G Minimum Voltage setting defines the minimum polarising voltage level. Where the measured polarising
voltage is below this level no directional output is given and. Operation of protection elements set as directional
will be inhibited. This prevents mal-operation under fuse failure/MCB tripped conditions where noise voltages can
be present.
©2010 Siemens Protection Devices Limited
) and the 67G Char Angle setting is added to this to adjust
ref
Angle + 67G Char Angle) and should be set to correspond with I
ref
°
°
(I lagging V by 15
) a 67G Char Angle of -15
°
°
(I lagging V by 45
) a 67G Char Angle of -45
7SR224 Argus Description of Operation
°
is required for maximum
°
is required for maximum
Chapter 1 Page 23 of 70
fault

Advertisement

Table of Contents
loading

Table of Contents