Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Default Static Variation reported when variation 0 requested: 2 (Binary Input with flags)
Default Change Event Variation reported when variation 0 requested: 2 (Binary Input with absolute time)
Point
Name/Description
Index
96
51G-4
97
50G-4
98
Cold Load Active
99
E/F Protection Out
100
P/F Inst Protection Inhibited
101
E/F Inst Protection Inhibited
102
SEF Inst Protection Inhibited
103
Ext Inst Protection Inhibited
105
Battery Test Pass
106
Battery Test Fail
107
Battery Ohms High
108
Battery Volts Low
109
Battery Volts High
110
Battery Healthy
112
Capacitor Ready
117
51SEF-1
118
50SEF-1
119
51SEF-2
120
50SEF-2
121
51SEF-3
122
50SEF-3
123
51SEF-4
124
50SEF-4
125
SEF Out
126
Trip Circuit Fail 1
127
Trip Circuit Fail 2
128
Trip Circuit Fail 3
129
CB Total Trip Count
130
CB Delta Trip Count
131
CB Count To AR Block
132
CB Frequent Ops Count
133
I^2t CB Wear
134
CB-A Reclaim
135
CB-A Lockout
136
CB-A Total Trip Count
137
CB-A Delta Trip Count
138
CB-A Count To AR Block
139
CB-A I^2t Wear
140
CB-A Frequent Ops Count
141
CB-A LO Handle Ops Count
142
CB-A 79 AR In progress
143
PhA Inst Protection Inhibited
144
50BF-1 Pole A
©2010 Siemens Protection Devices Limited
7SR224 Argus Data Comms
Default
Change Event
Assigned Class
(1, 2, 3 or none)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Chapter 4 Page 45 of 76