3.1.2 Instantaneous Overcurrent Protection (50)
Four elements are provided e.g. giving the option of using two elements set to forward and two to reverse.
Each instantaneous element (50-n) has independent settings. 50-n Setting for pick-up current and 50-n Delay
follower time delay. The instantaneous elements have transient free operation.
For the directional elements the direction of operation can be set using 50-n Dir. Control setting. Directional logic
is provided independently for each 50-n element.
Operation of the instantaneous overcurrent elements can be inhibited from:
Inhibit 50-n
79 P/F Inst Trips: 50-n
50-n Inrush Action: Inhibit
50-n VTS Action: Inhibit Operation of the VT Supervision function.
Figure 3.1-2 Logic Diagram: Instantaneous Over-current Element
©2010 Siemens Protection Devices Limited
A binary or virtual input, or function key.
When 'delayed' trips only are allowed in the autoreclose sequence
(79 P/F Prot'n Trip n = Delayed).
Operation of the inrush current detector function.
7SR224 Argus Description of Operation
Chapter 1 Page 19 of 70