Section 4: Modbus Definitions; Introduction - Siemens 7SR224 Technical Manual

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

Section 4: Modbus Definitions

4.1

Introduction

This section describes the MODBUS-RTU protocol implementation in the relays.
communication with a suitable control system.
This protocol can be set to use the Fibre Optic, RS232 and RS485 ports. The relay can communicate
simultaneously on all ports regardless of protocol used.
Each relay must be given an address to enable communication and can be set by the Communication
Interface:Relay Address. A relay with the default address of 0 will not be able to communicate.
Definitions with shaded area are not available on all relay models.
Coils (Read Write Binary values)
Address
Description
00001
Binary Output 1
00002
Binary Output 2
00003
Binary Output 3
00004
Binary Output 4
00005
Binary Output 5
00006
Binary Output 6
00007
Binary Output 7
00008
Binary Output 8
00009
Binary Output 9
00010
Binary Output 10
00011
Binary Output 11
00012
Binary Output 12
00013
Binary Output 13
00014
Binary Output 14
00015
Binary Output 15
00016
Binary Output 16
00017
Binary Output 17
00018
Binary Output 18
00019
Binary Output 19
00020
Binary Output 20
00021
Binary Output 21
00022
Binary Output 22
00023
Binary Output 23
00024
Binary Output 24
00025
Binary Output 25
00026
Binary Output 26
00027
Binary Output 27
00028
Binary Output 28
00029
Binary Output 29
00030
Binary Output 30
00031
Binary Output 31
00032
Binary Output 32
00100
LED Reset (Write only location)
00101
Settings Group 1
00102
Settings Group 2
00103
Settings Group 3
00104
Settings Group 4
00105
Settings Group 5
00106
Settings Group 6
00107
Settings Group 7
00108
Settings Group 8
00109
Circuit Breaker 1
©2010 Siemens Protection Devices Limited
7SR224 Argus Data Comms
This protocol is used for
Chapter 4 Page 26 of 76