Section 5: DNP3.0 Definitions

5.1

Device Profile

The following table provides a "Device Profile Document" in the standard format defined in the DNP 3.0 Subset
Definitions Document. While it is referred to in the DNP 3.0 Subset Definitions as a "Document," it is in fact a
table, and only a component of a total interoperability guide. The table, in combination with the Implementation
Table provided and the Point List Tables provided should provide a complete configuration/interoperability guide
for communicating with a device implementing the Triangle MicroWorks, Inc. DNP 3.0 Slave Source Code Library.
DNP V3.0
DEVICE PROFILE DOCUMENT
(Also see the DNP 3.0 Implementation Table Section 5.2.)
Vendor Name:
Siemens Protection Devices Ltd.
Device Name: 7SR224 , using the Triangle MicroWorks, Inc. DNP3 Slave Source Code Library, Version
3.
Highest DNP Level Supported:
For Requests:
For Responses:
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the
complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and
28 (index) are supported. Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers
00 or 01.
Output Event Object 11 is supported.
Maximum Data Link Frame Size (octets):
Transmitted: 256
Received
256
Maximum Data Link Re-tries:
None
Fixed (3)
Configurable from 0 to 65535
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable as: Never, Only for multi-frame messages, or Always
Requires Application Layer Confirmation:
Never
Always
When reporting Event Data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Sometimes
Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment
messages."
©2010 Siemens Protection Devices Limited
Level 3
Level 3
7SR224 Argus Data Comms
Device Function:
Master
Slave
Maximum Application Fragment Size (octets):
Transmitted: 2048
Received
2048
Maximum Application Layer Re-tries:
None
Configurable
Chapter 4 Page 35 of 76