Siemens 7SR224 Technical Manual page 180

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Default Static Variation reported when variation 0 requested: 2 (Binary Input with flags)
Default Change Event Variation reported when variation 0 requested: 2 (Binary Input with absolute time)
Point
Name/Description
Index
145
50BF-2 Pole A
146
Cap-A Ready
147
Cap-A Test Pass
148
Cap-A Test Fail
149
Cap-A Recovery Fail
150
Cap-A Test
151
CB-B Reclaim
152
CB-B Lockout
153
CB-B Total Trip Count
154
CB-B Delta Trip Count
155
CB-B Count To AR Block
156
CB-B I^2t Wear
157
CB-B Frequent Ops Count
158
CB-B LO Handle Ops Count
159
CB-B 79 AR In progress
160
PhB Inst Protection Inhibited
161
50BF-1 Pole B
162
50BF-2 Pole B
163
Cap-B Ready
164
Cap-B Test Pass
165
Cap-B Test Fail
166
Cap-B Recovery Fail
167
Cap-B Test
168
CB-C Reclaim
169
CB-C Lockout
170
CB-C Total Trip Count
171
CB-C Delta Trip Count
172
CB-C Count To AR Block
173
CB-C I^2t Wear
174
CB-C Frequent Ops Count
175
CB-C LO Handle Ops Count
176
CB-C 79 AR In progress
177
PhC Inst Protection Inhibited
178
50BF-1 Pole C
179
50BF-2 Pole C
180
Cap-C Ready
181
Cap-C Test Pass
182
Cap-C Test Fail
183
Cap-C Recovery Fail
184
Cap-C Test
185
Pole Discrepancy
186
LOV Primed
187
LOV Trip
188
LOV Close
189
LOV In Progress
190
BI 34
191
BI 35
192
BI 36
©2010 Siemens Protection Devices Limited
7SR224 Argus Data Comms
Default
Change Event
Assigned Class
(1, 2, 3 or none)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Chapter 4 Page 46 of 76

Advertisement

Table of Contents
loading

Table of Contents