Siemens 7SR224 Technical Manual page 186

Recloser controller
Hide thumbs Also See for 7SR224:
Table of Contents

Advertisement

Analogue Inputs
The following table lists Analogue Inputs (Object 30). It is important to note that 16-bit and 32-bit variations of
Analogue Inputs, Analogue Output Control Blocks, and Analogue Output Statuses are transmitted through DNP
as signed numbers.
The "Default Deadband," and the "Default Change Event Assigned Class" columns are used to represent the
absolute amount by which the point must change before an analogue change event will be generated, and once
generated in which class poll (1, 2, 3, or none) will the change event be reported.
The default analogue input event buffer size is set 30.
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Default Static Variation reported when variation 0 requested: 2 (16-Bit Analog Input with Flag)
Default Change Event Variation reported when variation 0 requested: 4 (16-Bit Analog Change Event with
Time)
Point
Name/Description
Index
0
Frequency (Hz)
1
Vab Primary (kV)
2
Vbc Primary (kV)
3
Vca Primary (kV)
4
Va Primary (kV)
5
Vb Primary (kV)
6
Vc Primary (kV)
7
Va Secondary (V)
8
Vb Secondary (V)
9
Vc Secondary (V)
21
Vzps Magnitude (V)
22
Vpps Magnitude (V)
23
Vnps Magnitude (V)
31
Ia Primary (kA)
32
Ib Primary (kA)
33
Ic Primary (kA)
34
Ia Secondary (A)
35
Ib Secondary (A)
36
Ic Secondary (A)
37
Ia Nominal Magnitude (xIn)
38
Ib Nominal Magnitude (xIn)
39
Ic Nominal Magnitude (xIn)
43
In Primary (kA)
44
In Secondary (A)
45
In Nominal (xIn)
46
Ig Primary (kA)
47
Ig Secondary (A)
48
Ig Nominal (xIn)
51
Izps Nominal Magnitude (xIn)
52
Ipps Nominal Magnitude (xIn)
53
Inps Nominal Magnitude (xIn)
57
Active Power A Phase W
58
Active Power B Phase W
59
Active Power C Phase W
60
3 Phase Real Power (P) (MW)
61
Reactive Power A Phase VAr
62
Reactive Power B Phase VAr
63
Reactive Power C Phase VAr
64
3 Phase Reactive Power (Q) (MVAr)
65
Apparent Power A Phase VA
©2010 Siemens Protection Devices Limited
Def.
Scaling
Deadband
Class
Factor
100.0
1
3
0.001
1000
3
0.001
1000
3
0.001
1000
3
0.001
1000
3
0.001
1000
3
0.001
1000
3
100.0
1
3
100.0
1
3
100.0
1
3
100.0
1
3
100.0
1
3
100.0
1
3
0.001
1000
3
0.001
1000
3
0.001
1000
3
100.0
1
3
100.0
1
3
100.0
1
3
100.0
1
3
100.0
1
3
100.0
1
3
0.001
1000
3
100.0
1
3
100.0
1
3
0.001
1000
3
100.0
1
3
100.0
1
3
100.0
1
3
100.0
1
3
100.0
1
3
0.000001
1000000
3
0.000001
1000000
3
0.000001
1000000
3
0.000001
100000
3
0.000001
1000000
3
0.000001
1000000
3
0.000001
1000000
3
0.000001
100000
3
0.000001
1000000
3
7SR224 Argus Data Comms
Def.
Def/
Static
Event
Object
Object
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
Chapter 4 Page 52 of 76