Restart Standby; Sibe34 - Daikin RXYSQ4-5-6PA7V1B Service Manual

Vrv iii-s
Table of Contents

Advertisement

Special Control
3.5

Restart Standby

Restart is stood by force to prevent frequent power-on/off and to equalize pressure in the
refrigerant system.
Actuator
Compressor
Outdoor unit fan
Four way valve
Main electronic expansion valve (EV1)
Subcooling electronic expansion valve
(EV3)
Hot gas bypass valve (SVP)
Ending conditions
58
Operation
OFF
Ta>30°C: STEP4
Ta≤30°C: OFF
Keep former condition.
0 pls
0 pls
OFF
2 min.
Remarks

SiBE34-802

Function