Specifications
Ceiling Mounted Built-in Type
1-1 TECHNICAL SPECIFICATIONS
Capacity
Cooling
(Conditions
Heating
specified in 1)
Cooling
Power input
(Nominal)
Heating
Colour
Casing
Material
Height
Packing
Width
Depth
Dimensions
Height
Unit
Width
Depth
Unit
Weight
Packed Unit
Required Ceiling Void
Length
Nr of Rows
Fin Pitch mm
Dimensions
Nr of Passes
Heat
Face Area m²
Exchanger
Nr of Stages
Tube type
Fin type
Fin
Treatment
Type
Fan
Quantity
High
Cooling
Low
Air Flow Rate
High
Heating
Low
High
External static
Standard Pa
pressure
Low
Quantity
Fan
Model
Steps
Motor
Output
(high)
Drive
Refrigerant
Name
Sound
Sound Level
Cooling
power
(nominal)
High
Sound
Cooling
Pressure
Low
High
Sound
Heating
Pressure
Low
Type
Liquid (OD)
Diameter mm
Type
Piping
Gas
connections
Diameter mm
Drain
Diameter mm
Heat Insulation
Model
Colour
Height
Decoration
Panel
Dimensions
Width
Depth
Weight
Drain-up Height
Air Filter
Air direction control
Refrigerant control
Temperature control
Safety devices
Standard Accessories
Notes
20
FXSQ63M8V3B
kW
7.10
kW
8.00
kW
0.189
kW
0.169
mm
354
mm
1192
mm
936
mm
300
mm
1000
mm
800
kg
41
kg
47
mm
350
mm
750
3
1.75
7
0.221
14
2
m³/min
21.00
m³/min
15.50
m³/min
21.00
m³/min
15.50
Pa
123
111
Pa
1
2D18H2AB1V1
W
125
dBA
56.0
dBA
35.0
dBA
30.0
dBA
35.0
dBA
30.0
9.5
15.9
32
BYBS71DJW1
mm
55
mm
1100
mm
500
kg
4.5
mm
600
PC board fuse, Drain pump
fuse, Fan motor thermal fuse
Metal clamp for drain hose, Paper pattern for installation, Drain hose, Insulation for fitting, Washer for hanger bracket,
Screws for duct flanges, Screws for fixing the paper pattern for installation, Fuse, Installation and operation manual
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
The external static pressure is changeable : change the connectors inside the electrical box, this pressure means :
The external static pressure is changeable : change the connectors inside the electrical box, this pressure means :
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
The sound pressure values are mentioned for a unit installed with rear suction
FXSQ80M8V3B
FXSQ100M8V3B
9.00
10.00
0.234
0.214
Non painted
Galvanised steel
356
1596
938
300
1400
800
51
58
350
1150
3
1.75
10
0.338
14
Hi-XSS (7)
Symmetric waffle louvre
Hydrophilic
Sirocco fan
3
27.00
20.00
27.00
20.00
141
125
98
1
3D18H2AH1V1
3D18H2AH1V1
step motor
135
Direct drive
R-410A
55.0
37.0
31.0
37.0
31.0
Flare connection
9.5
Flare connection
15.9
32
Both liquid and gas pipes
BYBS125DJW1
BYBS125DJW1
White (10Y9/0,5)
55
1500
500
6.5
600
Resin net with mold resistance
Up and downwards
Electronic expansion valve
Microprocessor thermostat for cooling and heating
PC board fuse, Drain pump fuse, Fan motor thermal protector
equivalent refrigerant piping : 8m, level difference : 0m.
equivalent refrigerant piping : 8m, level difference : 0m.
High static pressure -standard - low static pressure
High static pressure -standard
SiBE34-802
FXSQ125M8V3B
11.20
14.00
12.50
16.00
0.242
0.321
0.222
0.301
356
356
1596
1596
938
938
300
300
1400
1400
800
800
51
52
58
59
350
350
1150
1150
3
3
1.75
1.75
10
10
0.338
0.338
14
14
3
3
28.00
38.00
20.50
28.00
28.00
38.00
20.50
28.00
141
109
125
93
1
1
3D18H2AG1V1
135
225
56.0
65.0
38.0
40.0
33.0
35.0
38.0
40.0
33.0
35.0
9.5
9.5
15.9
15.9
32
32
BYBS125DJW1
55
55
1500
1500
500
500
6.5
6.5
600
600