Other Control

5.

Other Control

5.1

Demand Operation

In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using "Demand 1 Setting".
To operate the unit with this mode, additional setting of "Continuous Demand Setting".
[Demand 1 setting]
Demand 1 setting 1
Demand 1 setting 2 (factory setting)
Demand 1 setting 3
5.2

Heating Operation Prohibition

Heating operation is prohibited above 24°CDB outdoor air temperature.
64
Setting
Other protection control functions have precedence over the above operation.
Standard for upper limit of power consumption
Approx. 60%
Approx. 70%
Approx. 80%
SiBE34-802
Function