Field Setting
3.1.7
Centralized Control Group No. Setting
BRC1C Type
In order to conduct the central remote control using the central remote controller and the unified
ON/OFF controller, Group No. settings should be made by group using the operating remote
controller.
Make Group No. settings for central remote control using the operating remote controller.
1. Turn ON the power of the indoor unit and unified ON/OFF controller. (Unless the power is
2. While in normal mode, press and hold the "
3. Select the MODE No. "
4. Use the "
5. Press "
6. Press "
Note:
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.
100
ON, no setting can be made.)
Check that the installation and electrical wiring are correct before turning the power supply ON.
When the power supply is turned ON, all LCD appear once and the unit may not accept the
operation for about one minute with the display of "
and OFF)
more to set the system to "Field Setting Mode".
00
" with the "
" button to select the group No. for each group.
(Group numbers increase in the order of 1-00, 1-01, ... 1-15, 2-00, ... 4-15.)
" to set the selected group No.
" to return to the NORMAL MODE.
GROUP NO.
For wireless remote controller, see the following.
For setting group No. of HRV and wiring adaptor for other air conditioners, etc., refer to the
instruction manual attached.
" switch for a period of four seconds or
" button.
UNIT NO.
SETTING
TEST
5
SiBE34-802
"
flashing (an interval of ON, ON,
MODE NO.
FIELD SET
MODE
Test Operation